Piping insulation

• Execute heat insulation work completely on both sides of the 

gas piping and the liquid piping. Otherwise, a water leakage 
can result sometimes.

• When using a heat pump, the temperature of the gas piping 

can reach up to approximately 250°F, so use insulation 
which is sufficiently resistant.

• Also, in cases where the temperature and humidity of the refrig-

erant piping sections might exceed 86°F or RH80%, reinforce 
the refrigerant insulation. (13/16” or thicker) Condensation may 
form on the surface of the insulating material.

• Check the pipe connector for gas leaks, then insulate it as 

shown in the drawing below.

• Make absolutely sure to execute heat insulation works on the 

pipe-connecting section after checking gas leakage by thor-
oughly studying the following figure and using the attached 
heat insulating materials for fitting. (Fasten both ends with 
the clamps (accessory).) 

• Wrap the sealing pad (accessory) only around the insulation 

for the joints on the gas piping side. 

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

6-4

Brazing referigerant piping

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 2.9psi. with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping.

NOTE

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filter metal (BCuP) which 
does not require flux.
(Flux has extremely harmful infulence on refrigerant piping 
sysems. For instance, if the chlorine based flux is used, it 
will cause pipe corrosion or, in particular, if the flux contains 
fluorine, it will damage the refrigerant oil.)

7. DRAIN PIPING WORK

〈〈

Rig the drain pipe as shown below and take measures 

against condensation. Improperly rigged piping could lead 
to leaks and eventually wet furniture and belongings.

〉〉

(1) Carry out the drain piping

• The diameter of the drain pipe should be greater than or 

equal to the diameter of the connecting pipe (vinyl tube; 
pipe size: 13/16”; outer dimension: 1 1/4”).

• Keep the drain pipe short and sloping downwards at a gra-

dient of at least 1/100 to prevent air pockets from forming.

• If the drain hose cannot be sufficiently set on a slope, 

execute the drain raising piping.

• To keep the drain hose from sagging, space hanging 

wires every 3.28 to 4.92 ft..

NOTE

Setting the unit at an angle opposite to the drain piping 

might cause leaks.

• Use the drain hose and the metal clamp. Tighten the 

clamp firmly. Insert the drain hose into the drain socket, 
up to the tape. Tighten the clamp until the screw head is 
less than 3/16” from the hose.

• Wrap the sealing pad over the metal clamp and drain 

hose to insulate.

• Insulate the drain hose inside the building.

〈 

PRECAUTIONS FOR DRAIN RAISING PIPING 

〈 

HOW TO INSTALL PIPING 

(1) Connect the drain hose to the drain raising pipes, and 

insulate them.

(2) Connect the drain hose to the drain outlet on the indoor 

unit, and tighten it with the metal clamp.

(3) Insulate both metal clamp and drain hose with the seal-

ing pad.

Summary of Contents for FXMQ30MVJU

Page 1: ...in type FXSQ12MVJU FXSQ30MVJU FXSQ18MVJU FXSQ36MVJU FXSQ24MVJU FXSQ48MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in...

Page 2: ...RK 6 DRAIN PIPING WORK 7 ELECTRIC WIRING WORK 7 WIRING EXAMPLE AND HOW TO SET THE REMOTE CON TROLLER 8 SELECTING INSTALLATION SITE 11 PREPARATIONS BEFORE INSTALLATION 11 INDOOR UNIT INSTALLATION 12 RE...

Page 3: ...of refrig erant leakage Contact the place of purchase for more information Excessive refrigerant in a closed ambient can lead to oxygen deficiency Be sure to use only the specified accessories and pa...

Page 4: ...rts should be done in accordance with the relevant local and national regulations 2 BEFORE INSTALLATION When moving the unit while removing it from the carton box be sure to lift it by holding on to t...

Page 5: ...or and outdoor units power supply wiring and connecting wires at least 3 5ft away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of...

Page 6: ...e strong enough to bear the equipment s weight Use embedded inserts or anchor bolts with new buildings and hole in anchors with old buildings 5 INDOOR UNIT INSTALLATION Installing optional accessories...

Page 7: ...he installation method mentioned below After the work is finished make sure to check that there is no gas leak When you keep on tightening the flare nut with a spanner there is a point where the tight...

Page 8: ...n the unit is running so be sure to provide condensate trap on the condensate outlet See the figure In order to prevent foreign matter from building up inside the piping you should avoid curves as muc...

Page 9: ...rmly When attaching the electric parts box lid make sure no wires get caught in the edges Pass wiring through the wiring through holes to prevent damage to them Make sure the remote controller wiring...

Page 10: ...he INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller 6 Never connect power supply wiring to the terminal block for remote controller wiring A mistake of the sort could damage...

Page 11: ...SAJ25K36 FXSQ18MVJU 16 3 4 or more BYBS45DJW1 Installation not required 13 3 4 or more KSAJ25K56 FXSQ24MVJU 16 3 4 or more BYBS71DJW1 Installation not required 13 3 4 or more KSAJ25K80 FXSQ30 36 48MVJ...

Page 12: ...res at least 3 5 ft away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 3 5 ft may not be sufficient enough to eliminate the nois...

Page 13: ...force the ceiling to bearing the weight of the unit 5 INDOOR UNIT INSTALLATION Installing optional accessories except for the decoration panel before installing the indoor unit is easier As for the pa...

Page 14: ...he unit ventilate the room thoroughly right away 6 2 Connecting the refrigerant piping When connecting the flare nut coat the flare both inside and outside with ester oil or ether oil and initially ti...

Page 15: ...flared or a flanged connection Nitrogen should be set to 2 9psi with a pressure reducing valve if brazing while inserting nitrogen into the piping NOTE Do not use flux when brazing refrigerant piping...

Page 16: ...e unit Press to go back to the first mode You can check whether drainage is satisfactory or not by removing the access opening lid and checking the water level of the drain pan through the access open...

Page 17: ...remote controller is as follows 1 Outdoor unit Indoor unit Max 3280 ft Total wiring length 6560 ft 2 Indoor unit Remote controller Max 1640 ft 2 Insulated thickness 1 16 or more Model Power supply wi...

Page 18: ...pply terminal Looseness in the connection may cause overheating Use the specified electric wire Connect the wire securely to the terminal Lock the wire down without applying excessive force to the ter...

Page 19: ...CONNECTOR According to the system static pressure requirement reposi tion the adaptors of PC board inside the electric parts box as shown in the below drawings NOTE The unit is factory set for standar...

Page 20: ...CONTROL BY 2 REMOTE CONTROLLERS Con trolling 1 indoor unit by 2 remote controllers When using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER 1 Insert a screw dr...

Page 21: ...ORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when an malfunction occurs Check the malfunction...

Page 22: ...0403 HT 3P086156 9N EM03A042B Daikin US Corporation 375 Park Avenue Suite 3308 New York NY 10152 www daikinac com info daikinac com...

Reviews: