• Refer to the table below for the tightening torque of the
terminal screws.
3. Do not connect wires of different gauge to the same ground-
ing terminal. Looseness in the connection may deteriorate
protection.
4. Outside of the unit, keep transmission wiring at least
1 15/16” away from power supply wiring. The equipment
may malfunction if subjected to electrical (external) noise.
5. For remote controller wiring, refer to the “INSTALLATION
MANUAL OF REMOTE CONTROLLER” attached to the
remote controller.
6.
Never connect power supply wiring to the terminal
block for remote controller wiring. A mistake of the sort
could damage the entire system.
7. Use only specified wire and tightly connect wires to termi-
nals. Be careful wires do not place external stress on termi-
nals. Keep wiring in neat order and so as not to obstruct
other equipment such as popping open the electric parts
box lid. Make sure the lid closes tight. Incomplete connec-
tions could result in overheating, and in worse case, electric
shock or fire.
Continued to “COMMON ITEM” (P18)