• Gas pipes : might cause explosions or fire if gas leaks.
• Water pipes : no grounding effect if hard vinyl piping is 

used.

• Telephone ground wires or lightning rods : might cause 

abnormally high electric potential in the ground during 
lighting storms.

8-2

ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A) 
kW: Fan Motor Rated Output (W); FLA: Full Load Amps (A)

8-3

SPECIFICATIONS FOR FIELD SUPPLIED 
FUSES AND WIRE 

NOTE

1.

Allowable length of transmission wiring between indoor/
outdoor units and between the indoor unit and the remote 
controller is as follows. 

(1) Outdoor unit – Indoor unit: 

Max. 3280ft. (Total wiring length: 6560ft.) 

(2) Indoor unit – Remote controller: 

Max. 1640ft.

9. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER

9-1

HOW TO CONNECT WIRINGS 

(Remove the electric parts box lid and wire as shown in the fig-
ure below.)

CAUTION

• Be sure to attach the sealing material or putty (field supplied) 

to hole of wiring to prevent the infiltration of water as well as 
any insects and other small creatures from outside. Other-
wise a short-circuit may occur inside the electric parts box.

• When clamping the wires, be sure no pressure is applied to 

the wire connections by using the included clamping material 
to make appropriate clamps. Also, when wiring, make sure 
the lid on the electric parts box fits snugly by arranging the 
wires neatly and attaching the electric parts box lid firmly. 
When attaching the electric parts box lid, make sure no wires 
get caught in the edges. Pass wiring through the wiring 
through holes to prevent damage to them.

• Make sure the remote controller wiring, the wiring between 

the units, and other electrical wiring do not pass through the 
same locations outside of the unit, separating them by at 
least 1 15/16”, otherwise electrical noise (external static) 
could cause mistaken operation or breakage. 

NOTE

1.

Use round crimp-style terminals for connecting wires to the 
power supply terminal block. 

If unavailable, observe the following points when wiring.
• Do not connect wires of different gauge to the same 

power supply terminal.
(Looseness in the connection may cause overheating.)

• Use the specified electric wire. Connect the wire securely 

to the terminal. Lock the wire down without applying 
excessive force to the terminal. (Tightening torque: 
0.97ft.lbf ±10 %)

2. Tightening torque for the terminal screws.

• Use the correct screwdriver for tightening the terminal 

screws. If the blade of screwdriver is too small, the head 
of the screw might be damaged, and the screw will not be 
properly tightened.

• If the terminal screws are tightened too hard, screws 

might be damaged.

Units

Power supply

Fan motor

Model

Hz Volts

Voltage 

range

MCA MFA

W

FLA

FXMQ30MVJU

60

208-

230

Max. 253
Min.  187

1.6

15

160

1.3

FXMQ36MVJU

2.9

15

270

2.4

FXMQ48MVJU

4.4

15

430

3.5

Model

Power supply wiring

Remote controller wiring

Transmission wiring

Field fuses 

Size

Wire

Size

FXMQ30MVJU

15A

Wire size 
must  comply 
with local 
codes.

Sheathed 
wire 
(2 wire)

AWG

18-16

FXMQ36MVJU

FXMQ48MVJU

Summary of Contents for FXMQ30MVJU

Page 1: ...in type FXSQ12MVJU FXSQ30MVJU FXSQ18MVJU FXSQ36MVJU FXSQ24MVJU FXSQ48MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in...

Page 2: ...RK 6 DRAIN PIPING WORK 7 ELECTRIC WIRING WORK 7 WIRING EXAMPLE AND HOW TO SET THE REMOTE CON TROLLER 8 SELECTING INSTALLATION SITE 11 PREPARATIONS BEFORE INSTALLATION 11 INDOOR UNIT INSTALLATION 12 RE...

Page 3: ...of refrig erant leakage Contact the place of purchase for more information Excessive refrigerant in a closed ambient can lead to oxygen deficiency Be sure to use only the specified accessories and pa...

Page 4: ...rts should be done in accordance with the relevant local and national regulations 2 BEFORE INSTALLATION When moving the unit while removing it from the carton box be sure to lift it by holding on to t...

Page 5: ...or and outdoor units power supply wiring and connecting wires at least 3 5ft away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of...

Page 6: ...e strong enough to bear the equipment s weight Use embedded inserts or anchor bolts with new buildings and hole in anchors with old buildings 5 INDOOR UNIT INSTALLATION Installing optional accessories...

Page 7: ...he installation method mentioned below After the work is finished make sure to check that there is no gas leak When you keep on tightening the flare nut with a spanner there is a point where the tight...

Page 8: ...n the unit is running so be sure to provide condensate trap on the condensate outlet See the figure In order to prevent foreign matter from building up inside the piping you should avoid curves as muc...

Page 9: ...rmly When attaching the electric parts box lid make sure no wires get caught in the edges Pass wiring through the wiring through holes to prevent damage to them Make sure the remote controller wiring...

Page 10: ...he INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller 6 Never connect power supply wiring to the terminal block for remote controller wiring A mistake of the sort could damage...

Page 11: ...SAJ25K36 FXSQ18MVJU 16 3 4 or more BYBS45DJW1 Installation not required 13 3 4 or more KSAJ25K56 FXSQ24MVJU 16 3 4 or more BYBS71DJW1 Installation not required 13 3 4 or more KSAJ25K80 FXSQ30 36 48MVJ...

Page 12: ...res at least 3 5 ft away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 3 5 ft may not be sufficient enough to eliminate the nois...

Page 13: ...force the ceiling to bearing the weight of the unit 5 INDOOR UNIT INSTALLATION Installing optional accessories except for the decoration panel before installing the indoor unit is easier As for the pa...

Page 14: ...he unit ventilate the room thoroughly right away 6 2 Connecting the refrigerant piping When connecting the flare nut coat the flare both inside and outside with ester oil or ether oil and initially ti...

Page 15: ...flared or a flanged connection Nitrogen should be set to 2 9psi with a pressure reducing valve if brazing while inserting nitrogen into the piping NOTE Do not use flux when brazing refrigerant piping...

Page 16: ...e unit Press to go back to the first mode You can check whether drainage is satisfactory or not by removing the access opening lid and checking the water level of the drain pan through the access open...

Page 17: ...remote controller is as follows 1 Outdoor unit Indoor unit Max 3280 ft Total wiring length 6560 ft 2 Indoor unit Remote controller Max 1640 ft 2 Insulated thickness 1 16 or more Model Power supply wi...

Page 18: ...pply terminal Looseness in the connection may cause overheating Use the specified electric wire Connect the wire securely to the terminal Lock the wire down without applying excessive force to the ter...

Page 19: ...CONNECTOR According to the system static pressure requirement reposi tion the adaptors of PC board inside the electric parts box as shown in the below drawings NOTE The unit is factory set for standar...

Page 20: ...CONTROL BY 2 REMOTE CONTROLLERS Con trolling 1 indoor unit by 2 remote controllers When using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER 1 Insert a screw dr...

Page 21: ...ORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when an malfunction occurs Check the malfunction...

Page 22: ...0403 HT 3P086156 9N EM03A042B Daikin US Corporation 375 Park Avenue Suite 3308 New York NY 10152 www daikinac com info daikinac com...

Reviews: