ED36-212

Installation

FXH-L

263

7

Bolt Pitch

Drain Piping Work

Preparations Before Installation

(1) Relative positions of indoor unit, suspension bolt, piping hole, drain piping hole, and electric wire 

hole position. (Refer to Fig. 2)

Model

A

B

C

D

E

F

G

FXH32L

960

920

390

375

310

400

375

FXH63L

1160

1120

490

475

410

500

475

FXH100L

1400

1360

610

595

530

620

595

A (Decoration panel)

B (Suspension bolt pitch)

B (Suspension bolt pitch)

85

185

160

210

260

680 (Decor

ation panel)

C

D

E

Top side drain 
piping hole

Top liquid hole

Top gas piping hole

Suspension 
bolt (×4)

Air outlet

False ceiling view

(Length : mm)

Fig. 2

160

135

F

G

Rear side piping hole 
(

φ 

100 )

Left side piping hole

Front view

(2) Make the suspension bolt hole, piping hole, drain piping hole.

• Refer to the paper pattern for installation for hole positions.
• Fix the positions for suspension bolt, piping hole, drain piping hole, and electric wire hole, and make the 

openings.

3PN01417-5K-5

Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping could 
lead to leaks and eventually wet furniture and belongings.

(1) Rig drain piping 

• For drain work, rig the pipes so that they drain reliably.
• The drain pipe outlet direction can be chosen from the right rear, right, left rear, and left. Refer to 

“REFRIGERANT PIPING WORK” for right rear and right direction, and refer to Fig. 20 for left rear and 
left direction. 

• For left drain pipe outlet, remove the rubber plug and the insulation on the drain pipe connecting opening 

on the left side of the unit and change the position to the right side.

Rear side (metal plate) 
removable part

Left-facing drain piping

Left dressing board 
removable part

Rear left-facing drain piping

Fig. 20

3PN01417-5K-1C

Summary of Contents for FXH-L Series

Page 1: ...ed Type 1 Features 250 2 Specifications 251 3 Dimensions 252 4 Piping Diagrams 255 5 Wiring Diagrams 256 6 Capacity Tables 257 6 1 Cooling Capacity 257 6 2 Heating Capacity 258 7 Air Velocity and Temp...

Page 2: ...nd H L 32 36 31 63 39 34 100 45 37 dB A Low operating sound Uses the new silent stream fan and many more silent technologies Sound absor ption member Turbulent flow is produced Straightening vane New...

Page 3: ...rect Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and H...

Page 4: ...Dimensions ED36 212 252 FXH L 3 Dimensions FXH32LVE 3D027536B...

Page 5: ...ED36 212 Dimensions FXH L 253 7 FXH63LVE 3D027538B...

Page 6: ...Dimensions ED36 212 254 FXH L FXH100LVE 3D027539B...

Page 7: ...ED36 212 Piping Diagrams FXH L 255 7 4 Piping Diagrams Refrigerant pipe connection port diameters mm Model Gas Liquid FXH32L 12 7 6 4 FXH63L 15 9 9 5 FXH100L 19 1...

Page 8: ...Wiring Diagrams ED36 212 256 FXH L 5 Wiring Diagrams FXYHP 32K 63K 100KVE 3D034052...

Page 9: ...1 5 2 7 5 5 3 8 4 5 5 9 3 5 5 16 0 4 9 4 2 5 8 4 6 6 7 5 1 7 1 5 2 7 5 5 3 8 4 5 5 9 3 5 5 18 0 4 9 4 2 5 8 4 6 6 7 5 1 7 1 5 2 7 5 5 3 8 4 5 5 9 3 5 5 20 0 4 9 4 2 5 8 4 6 6 7 5 1 7 1 5 2 7 5 5 3 8...

Page 10: ...4 0 3 8 3 7 3 4 63 13 7 15 0 5 6 5 5 5 4 5 4 5 3 5 3 11 8 13 0 5 8 5 8 5 7 5 6 5 6 5 5 9 8 11 0 6 1 6 0 6 0 5 9 5 9 5 8 9 5 10 0 6 3 6 2 6 1 6 1 6 0 5 9 8 5 9 1 6 4 6 3 6 2 6 2 6 1 6 1 7 0 7 6 6 6 6 5...

Page 11: ...emperature Distributions Reference Data FXH L 259 7 7 Air Velocity and Temperature Distributions Reference Data FXH100L Heating Air Velocity Distribution Center Air Flow FXH100L Heating Temperature Di...

Page 12: ...Electric Characteristics ED36 212 260 FXH L 8 Electric Characteristics 4D035304...

Page 13: ...s 2 These operating values were obtained in a dead room conversion values Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of the particul...

Page 14: ...leave a space of 200 mm or more between the unit and it s surroundings easier maintenance and service Where piping between indoor and outdoor units is possible within the allowable limit Refer to the...

Page 15: ...pattern for installation for hole positions Fix the positions for suspension bolt piping hole drain piping hole and electric wire hole and make the openings 3PN01417 5K 5 Rig the drain pipe as shown b...

Page 16: ...ulate Refer to Fig 23 No folding of drain hose inside the indoor unit Refer to Fig 24 If there is slack in the drain hose it may cause damage to the intake grill 2 Confirm that smooth drainage is achi...

Page 17: ...ilter Resin net KAFJ501D56 KAFJ501D80 KAFJ501D112 3 L type piping kit for upward direction KHFJ5F50 KHFJ5F80 KHFJ5F160 Name 1 Drain hose 2 Clamp metal 3 Washer for hanging bracket 4 Clamp 5 Paper pat...

Page 18: ...ipe bellow elbow only bellow hose for VP20 All units of drain up height was unified to 600mm From the bottom of the ceiling Wiring diagram L Shape Connection Pipe Kit Application purpose This kit must...

Reviews: