![background image](http://html1.mh-extra.com/html/daikin/fxh-l-series/fxh-l-series_manual_2459721016.webp)
Installation
ED36-212
264
FXH-L
• Insert the rubber stopper securely, all the way to the base, in order to prevent water leakage.
• The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe.
(Vinyl tube; pipe size: 20 mm; outer dimension: 26 mm)
• Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets
from forming. (Refer to Fig. 21)
• Use the attached drain hose (1) and clamp (2).
Insert the drain hose into the drain socket, up to the gray tape.(Refer to Fig. 22)
Tighten the clamp until the screw head is less than 4 mm from the hose. (Refer to Fig. 23)
(Be careful of the installation direction. Install so that the clamp metal does not contact the intake grill.)
• Wrap the attached sealing pad (8) over the clamp and drain hose to insulate. (Refer to Fig. 23)
• No folding of drain hose inside the indoor unit. (Refer to Fig. 24)
(If there is slack in the drain hose, it may cause damage to the intake grill.)
(2) Confirm that smooth drainage is achieved after the piping work.
• Add 600 cc of water in the drain pan from the air outlet for confirming drainage. (Refer to Fig. 25)
CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sew-
age might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Wrong
Fig. 24
Sealing
pad (8)
(attached)
Clamp metal (2)
(attached)
Sealing pad (8)
(attached)
Clamp metal (2)
(attached)
≤
4
≤
4
(Length : mm)
< Facing rear right or right >
< Facing rear left or left >
Fig. 23
Taping area
(Gray)
Drain hose (1)
(attached)
Clamp metal (2) (attached)
Fig. 22
Tilt down
Do not lift
(When drain hose is connected)
Make sure there
is no slack
Make sure it is
not in the water
Good
Wrong
Fig. 21
Air outlet
Pump used for
kerosene stoves.
Bucket
Fig. 25
3PN01417-5K-11
Summary of Contents for FXH-L Series
Page 4: ...Dimensions ED36 212 252 FXH L 3 Dimensions FXH32LVE 3D027536B...
Page 5: ...ED36 212 Dimensions FXH L 253 7 FXH63LVE 3D027538B...
Page 6: ...Dimensions ED36 212 254 FXH L FXH100LVE 3D027539B...
Page 8: ...Wiring Diagrams ED36 212 256 FXH L 5 Wiring Diagrams FXYHP 32K 63K 100KVE 3D034052...
Page 12: ...Electric Characteristics ED36 212 260 FXH L 8 Electric Characteristics 4D035304...