Installation
ED36-212
262
FXH-L
10. Installation
Installation Example
Air outlet
Drain pipe
Refrigerant pipe
Grounding wire
Remote controller
Suction grille
Air filter (inside suction grille)
Transmission wiring
Air flow flap (at air outlet)
Conducts electricity from the unit into the
ground to prevent electric shock.
3PN02401-4F
Service Space (Selecting Installation Site)
(1) Select an installation site where the following conditions are fulfilled and that meets your cus-
tomer’s approval.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• If supporting structural members are not strong enough to take the unit’s weight, the unit could fall out
of place and cause serious injury.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service can be ensured. (Refer to Fig. 1)
If sufficient clearance could be ensured at*, leave a space of 200 mm or more between the unit and it’s
surroundings easier maintenance and service.
• Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the instal-
lation manual for the outdoor unit.)
• Keep the indoor and outdoor units, power cable and transmission wiring, at least 1 m from TVs and
radios, to prevent distorted pictures and static. (Depending on the type and source of the electrical
waves, static may be heard even when more than 1 m away.)
(2) Use suspension bolts for installation. Check whether the ceiling is strong enough to support the
weight of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
(Installation pitch is marked on the paper pattern for installation. Refer to it to check for points requiring
reinforcing.)
(3) This indoor unit may be installed on ceilings up to 3.5 m in height. However, if the ceiling is higher
than 2.7m, the remote control will have to be set locally.
*
≥
30
*
≥
30
≥
300
2500 or higher
from the floor
For installation
in high places
Air inlet
Air outlet
Obstruction
Floor
Required service
space
(Length : mm)
Fig. 1
3PN01417-5K-4
Summary of Contents for FXH-L Series
Page 4: ...Dimensions ED36 212 252 FXH L 3 Dimensions FXH32LVE 3D027536B...
Page 5: ...ED36 212 Dimensions FXH L 253 7 FXH63LVE 3D027538B...
Page 6: ...Dimensions ED36 212 254 FXH L FXH100LVE 3D027539B...
Page 8: ...Wiring Diagrams ED36 212 256 FXH L 5 Wiring Diagrams FXYHP 32K 63K 100KVE 3D034052...
Page 12: ...Electric Characteristics ED36 212 260 FXH L 8 Electric Characteristics 4D035304...