background image

FXFQ20~125M8V3B
VRV System air conditioners
4PW25082-1A

Installation and operation manual

4

When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand 3 or
4 turns before tightening firmly. 
Coat here with ether oil or ester oil

Check the pipe connector for gas leaks, then insulate it as
shown in the figure below.

If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a fire.

Finally make sure there is no refrigerant gas leak. A toxic gas
may be released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.

D

RAIN

 

PIPING

 

WORK

Rig the drain piping as shown in figure and take measures against
condensation. Improperly rigged piping could lead to leaks and
eventually wet furniture and belongings.

1.

Install the drain pipes.

Keep piping as short as possible and slope it downwards so that
air may not remain trapped inside the pipe. 

Keep pipe size equal to or greater than that of the connecting
pipe (Vinyl pipe of 25 mm nominal diameter and 32 mm outer
diameter).

Insert the supplied drain hose into the drain socket, up to the
white tape.

Tighten the clamp until the screw head is less then 4 mm from the
hose. 

Insulate the drain hose inside the building.

If the drain hose cannot be sufficiently set on a slope, fit the hose
with drain raising piping (field supply). 

How to perform piping 

(See figure 8)

1

Connect the drain hose to the drain raising pipes, and insulate
them.

2

Connect the drain hose to the drain outlet on the indoor unit, and
tighten it with the clamp.

Precautions

Install the drain raising pipes at a height of less than 550 mm.

Install the drain raising pipes at a right angle to the indoor unit
and no more than 300 mm from the unit.

2.

After piping work is finished, check if drainage flows
smoothly.

Open the water inlet lid, add approximately 2 l of water gradually
and check the drainage flow.

Method of adding water. See 

figure 13

.

When electric wiring work is finished

Check drainage flow during COOL running, explained in chapter
"

Test operation

".

When electric wiring work is not finished

Remove the switch box lid and connect the power supply and
remote controller to the terminals.
See 

figure 12

.

Next, press the inspection/test operation button 

 on the

remote controller. The unit will engage the test operation mode.

Press the operation mode selector button 

 until selecting fan

operation 

. Then, press the on/off button 

. The indoor unit

fan and drain pump will start up. Check that the water has drained

from the unit. Press 

 to go back to the first mode.

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting of liquid line 
(supplied with the unit) 

4

Insulation for fitting of gas line (sup-
plied with the unit) 

5

Clamps 
(use 2 clamps per insulation)

1

Hanging bar

1

Clamp metal (supplied with 
the unit)

2

Drain hose (supplied with 
the unit)

3

White tape (field supply)

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

5

4

2

1

3

1-1.5 m

1

2

1

3

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does not
have to stand additional force.

To  ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.

If unifying multiple drain pipes, install the pipes as
shown in 

figure 9

.  Select converging drain pipes

whose gauge is suitable for the operating capacity
of the unit.

1

T-joint converging drain pipes

1

Portable pump

2

Drain pipe

3

Service cover

4

Inspection opening

5

Service drain outlet (with rubber plug) (Use this outlet to drain 
water from the drain pan)

6

Plastic watering can (Tube should be about 100 mm long.) 
(Adding water through air discharge outlet)

7

Bucket (Adding water from inspection opening)

1

Switch box lid (1)

2

Power supply

3

Power supply terminal board

4

Rubber bush A

5

Clamp A

6

Switch box lid (2) with wiring diagram label

7

Transmission wiring

8

Terminal board for transmission wiring

9

Rubber bush B

10

Clamp B

11

Outside of the unit

12

Inside of the unit

13

Cable (power supply or transmission wiring)

14

Opening for the cable

15

Small sealing (supplied with the unit)

TEST

TEST

Summary of Contents for FXFQ20M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20M8V3B FXFQ25M8V3B FXFQ32M8V3B FXFQ40M8V3B FXFQ50M8V3B FXFQ63M8V3B FXFQ80M8V3B FXFQ100M8V3B FXFQ125M8V3B System air conditioners...

Page 2: ...840 780 5 6 7 8 680 840 860 910 950 12 12 3 5 10 1 8 6 7 11 12 15 4 2 14 7 9 13 4 4 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 6 6 1 2 3 4 7 7 7 1 4 6 3 5 2 3 18 mm 8 8 5 75 550 750 220 300...

Page 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Page 4: ...sories are included with your unit Optional accessories There are two types of remote controllers wired and wireless Select a remote controller according to customers request and install in an appropr...

Page 5: ...ad kit and to the chapter Field setting See figure 1 air flow direction 4 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If t...

Page 6: ...equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four c...

Page 7: ...ng water See figure 13 When electric wiring work is finished Check drainage flow during COOL running explained in chapter Test operation When electric wiring work is not finished Remove the switch box...

Page 8: ...es Precautions 1 Observe the notes mentioned below when wiring to the power supply terminal board Do not connect wires of different gauge to the same power supply terminal Looseness in the connection...

Page 9: ...100 hrs 1 Long life filter type Change the setting when ultra long life filter is installed This setting is important for time between 2 filter cleaning display indications refer to 10 0 0X Long life...

Page 10: ...No 12 then set the first code switch No to 1 Then set second code position No to 01 for forced off and to 02 for on off operation forced off at factory set See figure 22 Centralized control For centr...

Page 11: ...or wash the air filter with water When the air filter is very dirty use a soft brush and neutral detergent Remove water and dry in the shade 4 Fix the air filter Attach the air filter to the suction...

Page 12: ...attach the suction grill See item No 2 5 Close the suction grill See item No 1 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in acco...

Page 13: ...DIODE SERVICE MONITOR RED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 S...

Page 14: ...NOTES NOTES...

Page 15: ...1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 20 20 S M S S M 2 3 1 17 17 18 18 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 16 16 L...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25082 1A...

Reviews: