When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and
the other to "SUB".

Main/sub changeover

1.

Insert a wedge-head screwdriver into the recess between the upper
and lower part of the remote controller and, working from the
2 positions, pry off the upper part. 

(See figure 17)

(The remote controller PC board is attached to the upper part of
the remote controller.)

2.

Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". 

(See figure 20)

(Leave the switch of the other remote controller set to "M".)

Computerised control (forced off and on/off operation)

1.

Wire specifications and how to perform wiring.

Connect input from outside to terminals T1 and T2 of the terminal
board (remote controller to transmission wiring).

See 

figure 19

2.

Actuation

The following table explains "forced off" and "on/off operations" in
response to input A.

3.

How to select forced off and on/off operation

Turn the power on and then use the remote controller to select
operation.

Set the remote controller to the field set mode. For details, refer to
the chapter "How to set in the field", in the remote controller
manual.

When in the field set mode, select mode No. 12, then set the first
code (switch) No. to “1”. Then set second code (position) No. to
“01” for forced off and to “02” for on/off operation. (forced off at
factory set.) 

(See figure 22)

Centralized control

For centralized control, it is necessary to designate the group
No. For details, refer to the manual of each optional controller for
centralized control.

I

NSTALLATION

 

OF

 

THE

 

DECORATION

 

PANEL

Refer to the installation manual attached to the decoration panel.

After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop.

T

EST

 

OPERATION

Refer to the installation manual of the outdoor unit.

The operation lamp of the remote controller will flash when an
error occurs. Check the error code on the liquid crystal display to
identify the trouble. An explanation of error codes and the
corresponding trouble are provided on "Caution for servicing" of
the indoor unit.

1

Remote controller PC board

2

Factory setting

3

Only one remote controller needs to be changed

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75-1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum applicable load 

of 15 V DC, 10 mA

1

Input A

Forced off

on/off operation

Input "on" stops operation

input off 

 on: turns on the unit 

(impossible by remote controllers)

Input "off" enables control

input on 

 off: turns off the unit 

(by remote controller)

1

Second code No.

2

Mode No.

3

First code No.

4

Field set mode

1

Drain pumping device (built-in) drain water is removed from the 
room during cooling

2

Air flow flap (at air outlet)

3

Air outlet

4

Remote controller

5

Suction grill

6

Air filter (inside suction grill)

1

2

4

4

3

5

6

Summary of Contents for FXFQ20M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20M8V3B FXFQ25M8V3B FXFQ32M8V3B FXFQ40M8V3B FXFQ50M8V3B FXFQ63M8V3B FXFQ80M8V3B FXFQ100M8V3B FXFQ125M8V3B System air conditioners...

Page 2: ...840 780 5 6 7 8 680 840 860 910 950 12 12 3 5 10 1 8 6 7 11 12 15 4 2 14 7 9 13 4 4 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 6 6 1 2 3 4 7 7 7 1 4 6 3 5 2 3 18 mm 8 8 5 75 550 750 220 300...

Page 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Page 4: ...sories are included with your unit Optional accessories There are two types of remote controllers wired and wireless Select a remote controller according to customers request and install in an appropr...

Page 5: ...ad kit and to the chapter Field setting See figure 1 air flow direction 4 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If t...

Page 6: ...equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four c...

Page 7: ...ng water See figure 13 When electric wiring work is finished Check drainage flow during COOL running explained in chapter Test operation When electric wiring work is not finished Remove the switch box...

Page 8: ...es Precautions 1 Observe the notes mentioned below when wiring to the power supply terminal board Do not connect wires of different gauge to the same power supply terminal Looseness in the connection...

Page 9: ...100 hrs 1 Long life filter type Change the setting when ultra long life filter is installed This setting is important for time between 2 filter cleaning display indications refer to 10 0 0X Long life...

Page 10: ...No 12 then set the first code switch No to 1 Then set second code position No to 01 for forced off and to 02 for on off operation forced off at factory set See figure 22 Centralized control For centr...

Page 11: ...or wash the air filter with water When the air filter is very dirty use a soft brush and neutral detergent Remove water and dry in the shade 4 Fix the air filter Attach the air filter to the suction...

Page 12: ...attach the suction grill See item No 2 5 Close the suction grill See item No 1 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in acco...

Page 13: ...DIODE SERVICE MONITOR RED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 S...

Page 14: ...NOTES NOTES...

Page 15: ...1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 20 20 S M S S M 2 3 1 17 17 18 18 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 16 16 L...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25082 1A...

Reviews: