background image

FXFQ20~125M8V3B
VRV System air conditioners
4PW25082-1A

Installation and operation manual

6

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire. 

W

IRING

 

EXAMPLE

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 21

.

Complete system example (3 systems)

See figures 

14

16

 and 

18

.

When using 1 remote controller for 1 indoor unit. (Normal
operation.) 

(See figure 14)

.

For group control or use with 2 remote controllers 

(See figure 16)

.

When including BS unit 

(See figure 18)

.

Precautions

1.

A single switch can be used to supply power to units on the same
system. However, branch switches and branch circuit breakers must
be selected carefully.

2.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

3.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

F

IELD

 

SETTING

Field setting must be made from the remote controller in accordance
with the installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field setting" in the
installation manual of the remote controller.

Summary of field settings

1

Power supply

2

Main switch

3

Power supply wiring

4

Transmission wiring

5

Switch

6

Fuse

7

BS unit REYQ only

8

Indoor unit

9

Remote controller

1

Outdoor unit

2

Indoor unit

3

Remote controller (Optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

6

BS unit

NOTE

It is not necessary to designate indoor unit address
when using group control. The address is automati-
cally set when the power is activated.

Mode 

No.

(Note 1)

First 

code 

No.

Description of setting

Second code No. (Note 2)

01

02

03

04

10 

(20)

0

Filter contamination 
- Heavy/Light
= Setting to define 
time between 2 filter 
cleaning display 
indications. (When 
contamination is 
high, setting can be 
changed to half the 
time inbetween 2 
filter cleaning 
display indications.)

Ultra-
long-life 
filter

Light

±10,000 hrs.

Hea

vy

±5,000 hrs.

Long-life 
filter

±2,500 hrs.

±1,250 hrs.

Standard 
filter

±200 hrs.

±100 hrs.

1

Long-life filter type
Change the setting when ultra-
long-life filter is installed.
This setting is important for time 
between 2 filter cleaning display 
indications (refer to 10-0-0X).

Long-life filter

Ultra-long-life 
filter

2

Thermostat sensor selection

Use both the 
unit sensor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. 
(See note 5+6)

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 5+6)

Use remote 
controller 
sensor only. 
(See note 5+6)

3

Setting for display of time 
between 2 filter cleaning display 
indications

Display

Do not display

5

Information to I-manager, 
I-touch controller

Only unit sensor 
value (or remote 
sensor value if 
installed).

Sensor value as 
set by 10-2-0X 
or 10-6-0X.

6

Thermostat sensor in group 
control

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 6)

Use both the 
unit senor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. (See 
note 4+5+6)

12 

(22)

0

Output signal X1-X2 of the 
optional KRP1B PCB kit

Thermostat-on + 
compressor run

Operation

Mal-
function

1

ON/OFF input from outside 
(T1/T2 input) = Setting when 
forced ON/OFF is to be 
operated from outside.

Forced OFF

ON/OFF
operation

2

Thermostat differential 
changeover = Setting when 
remote sensor is used.

1°C

0.5°C

3

Fan setting during thermostat 
OFF at heating operation

LL

Set speed

OFF 
(See note 3)

4

Differential automatic 
changeover

0°C

1°C

2°C

3°C
(See 
note 7)

5

Auto-restart after power failure

Disabled

Enabled

9

Fixed cool/heat master

Disabled

Enabled

13 

(23)

0

Setting for air outlet velocity 
This setting is to be changed in 
function of ceiling height.

2.7 m

>2.7 

3.0 m

>3.0 

3.5 m

1

Selection for air flow direction
This setting is to be changed 
when blocking pad optional kit 
is used.

4-way flow

3-way flow

2-way flow

4

Airflow direction range setting
This setting is to be changed 
when range of swing flap 
movement needs to be 
changed.

Upper

Normal

Lower

5

Setting for adjustment of fan 
speed (phase control)

Standard

Option 1

Option 2

15 

(25)

3

Drain pump ope 
humidifier interlock

Equipped

Not equipped

Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected, 

indoor units can also be set individually.

Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 : If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01, 

10-2-02 or 10-2-03 have priority.

Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group 

connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have 
priority.

Note 7 : More settings for Differential automatic change over temperatures are:

Second code No.

05

4°C

06

5°C

07

6°C

08

7°C

Summary of Contents for FXFQ20M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20M8V3B FXFQ25M8V3B FXFQ32M8V3B FXFQ40M8V3B FXFQ50M8V3B FXFQ63M8V3B FXFQ80M8V3B FXFQ100M8V3B FXFQ125M8V3B System air conditioners...

Page 2: ...840 780 5 6 7 8 680 840 860 910 950 12 12 3 5 10 1 8 6 7 11 12 15 4 2 14 7 9 13 4 4 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 6 6 1 2 3 4 7 7 7 1 4 6 3 5 2 3 18 mm 8 8 5 75 550 750 220 300...

Page 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Page 4: ...sories are included with your unit Optional accessories There are two types of remote controllers wired and wireless Select a remote controller according to customers request and install in an appropr...

Page 5: ...ad kit and to the chapter Field setting See figure 1 air flow direction 4 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If t...

Page 6: ...equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four c...

Page 7: ...ng water See figure 13 When electric wiring work is finished Check drainage flow during COOL running explained in chapter Test operation When electric wiring work is not finished Remove the switch box...

Page 8: ...es Precautions 1 Observe the notes mentioned below when wiring to the power supply terminal board Do not connect wires of different gauge to the same power supply terminal Looseness in the connection...

Page 9: ...100 hrs 1 Long life filter type Change the setting when ultra long life filter is installed This setting is important for time between 2 filter cleaning display indications refer to 10 0 0X Long life...

Page 10: ...No 12 then set the first code switch No to 1 Then set second code position No to 01 for forced off and to 02 for on off operation forced off at factory set See figure 22 Centralized control For centr...

Page 11: ...or wash the air filter with water When the air filter is very dirty use a soft brush and neutral detergent Remove water and dry in the shade 4 Fix the air filter Attach the air filter to the suction...

Page 12: ...attach the suction grill See item No 2 5 Close the suction grill See item No 1 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in acco...

Page 13: ...DIODE SERVICE MONITOR RED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 S...

Page 14: ...NOTES NOTES...

Page 15: ...1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 20 20 S M S S M 2 3 1 17 17 18 18 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 16 16 L...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25082 1A...

Reviews: