background image

FXFQ20~125M8V3B
VRV System air conditioners
4PW25082-1A

Installation and operation manual

2

Notes to the installer

Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

S

ELECTING

 

INSTALLATION

 

SITE

When the conditions in the ceiling are exceeding 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, an
additional insulation is required (minimum 10 

mm thickness,

polyethylene foam).

For this unit you can select different air flow directions. It is necessary
to purchase an optional blocking pad kit to discharge the air in 2 or 3
directions.

1

Select an installation site where the following conditions
are fulfilled and that meets your customer's approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate water can be properly drained.

Where the false ceiling is not noticeably on an incline.

Where sufficient clearance for maintenance and service can be
ensured.

Where piping between indoor and outdoor units is possible within
the allowable limit. (Refer to the installation manual of the outdoor
unit.)

This is a class A product. In a domestic environment this product
may cause radio interference in which case the user may be
required to take adequate measures.

Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions and
radios. This is to prevent image interference and noise in those
electrical appliances.
(Noise may be generated depending on the conditions under
which the electric wave is generated, even if 1 meter is kept.)

2

Ceiling height

This indoor unit may be installed on ceilings up to 3.5 m in
height (for 80~125 units: 4.2 m). However, it becomes necessary
to make field settings by the remote controller when installing
the unit at a height over 2.7 m (for 80~125 units: 3.2 m). To avoid
accidental touching, it is recommended to install the unit higher
than 2.5 m.
Refer to the chapter "

Field setting

" and to the decoration panel

installation manual.

3

Air flow directions

Select the air flow directions best suited to the room and point of
installation. (For air discharge in 2 or 3 directions, it is necessary
to make field settings by means of the remote controller and to
close the air outlet(s). Refer to the installation manual of the
optional blocking pad kit and to the chapter "

Field setting

".) (See

figure 1

 (

 = air flow direction))

4

Use suspension bolts for installation. Check whether the
ceiling is strong enough to support the weight of the indoor
unit. If there is a risk, reinforce the ceiling before installing
the unit.

(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring reinforcing.)
Space required for installation see 

figure 2

  (

  = air flow

direction)

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1.

Relation of ceiling opening to unit and suspension bolt
position. 

(See figure 3)

Installation is possible when opening dimensions are as follows.
When installing the unit within the frame for fixing ceiling
materials. 

(See figure 4)

2.

Make the ceiling opening needed for installation where
applicable. (For existing ceilings.)

Refer to the paper pattern for installation for the ceiling opening
dimensions.

Create the ceiling opening required for installation. From the side
of the opening to the casing outlet, implement the refrigerant and
drain piping and wiring for remote controller (unnecessary for
wireless type) and indoor-outdoor unit casing outlet. Refer to
each piping or wiring section.

After making an opening in the ceiling, it may be necessary to
reinforce ceiling beams to keep the ceiling level and to prevent it
from vibrating. Consult the builder for details.

3.

Install the suspension bolts. (use either a W3/8 or M10 size bolt.)

Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to reinforce the
ceiling in order to bear the weight of the unit. Adjust clearance from
the ceiling before proceeding further.

Installation example see 

figure 5

.

1

Air discharge in 4 directions

2

Air discharge in 3 directions

3

Air discharge in 2 directions

1

Air discharge

2

Air inlet

NOTE

Leave 200 mm or more space where marked with *; on
sides where the air outlet is closed.

Model

H

FXFQ20~63

240

FXFQ80~125

298

1

Refrigerant piping

2

Suspension bolt (x4)

3

Hanger bracket

4

False ceiling

5

Suspension bolt pitch

6

Indoor unit

7

Ceiling opening

8

Decoration panel

1

Dimensions inside frame

2

Opening dimension inside the frame for ceiling

3

Frame

4

Ceiling material

5

Ceiling opening dimension

6

Ceiling-panel overlapping dimension

NOTE

Installation is possible with a ceiling dimension of
910 mm (marked with*). However, to achieve a ceiling-
panel overlapping dimension of 20 mm, the spacing
between the ceiling and the unit should be 35 mm or
less. If the spacing between ceiling and the unit is over
35 mm, attach ceiling material to the part or recover
the ceiling.

1

Ceiling slab

2

Anchor

3

Long nut or turn-buckle

4

Suspension bolt

5

False ceiling

NOTE

All the above parts are field supplied.

For other installation than standard installation, contact
your Daikin dealer for details.

Summary of Contents for FXFQ20M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20M8V3B FXFQ25M8V3B FXFQ32M8V3B FXFQ40M8V3B FXFQ50M8V3B FXFQ63M8V3B FXFQ80M8V3B FXFQ100M8V3B FXFQ125M8V3B System air conditioners...

Page 2: ...840 780 5 6 7 8 680 840 860 910 950 12 12 3 5 10 1 8 6 7 11 12 15 4 2 14 7 9 13 4 4 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 6 6 1 2 3 4 7 7 7 1 4 6 3 5 2 3 18 mm 8 8 5 75 550 750 220 300...

Page 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Page 4: ...sories are included with your unit Optional accessories There are two types of remote controllers wired and wireless Select a remote controller according to customers request and install in an appropr...

Page 5: ...ad kit and to the chapter Field setting See figure 1 air flow direction 4 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If t...

Page 6: ...equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four c...

Page 7: ...ng water See figure 13 When electric wiring work is finished Check drainage flow during COOL running explained in chapter Test operation When electric wiring work is not finished Remove the switch box...

Page 8: ...es Precautions 1 Observe the notes mentioned below when wiring to the power supply terminal board Do not connect wires of different gauge to the same power supply terminal Looseness in the connection...

Page 9: ...100 hrs 1 Long life filter type Change the setting when ultra long life filter is installed This setting is important for time between 2 filter cleaning display indications refer to 10 0 0X Long life...

Page 10: ...No 12 then set the first code switch No to 1 Then set second code position No to 01 for forced off and to 02 for on off operation forced off at factory set See figure 22 Centralized control For centr...

Page 11: ...or wash the air filter with water When the air filter is very dirty use a soft brush and neutral detergent Remove water and dry in the shade 4 Fix the air filter Attach the air filter to the suction...

Page 12: ...attach the suction grill See item No 2 5 Close the suction grill See item No 1 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in acco...

Page 13: ...DIODE SERVICE MONITOR RED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 S...

Page 14: ...NOTES NOTES...

Page 15: ...1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 20 20 S M S S M 2 3 1 17 17 18 18 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 16 16 L...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25082 1A...

Reviews: