Installation and operation manual

5

FXFQ20~125M8V3B

VRV System air conditioners

4PW25082-1A

E

LECTRIC

 

WIRING

 

WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".

All wiring must be performed by an authorized electrician.

A circuit breaker capable of shutting down power supply to the
entire system must be installed.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.

This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal board wiring to
the outdoor unit and BS unit are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.

Electrical characteristics

MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)

Specifications for field supplied fuses and wire

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring 

(See figure 12)

Power supply wiring
Remove the switch box lid (1) and connect the wires to the
power supply terminal board inside. While doing this, pull the
wires inside through the rubber bush A and clamp the wires
along with other wires using clamp A, untightening the clip of
clamp A by pressing. After the connection, tighten clamp A as
before.

Unit wiring and remote controller wiring
Remove the switch box lid (2) and pull the wires inside through
the rubber bush B and connect to the terminal board for unit
transmission wiring.

After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing into
the required number of pieces and wrap them around all the
cables.

Precautions

1

Observe the notes mentioned below when wiring to the power
supply terminal board.

Do not connect wires of different gauge to the same power supply
terminal. (Looseness in the connection may cause overheating.)

When connecting wires of the same gauge, connect them
according to the figure.

Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. (tightening torque 1.31 N•m ±10 %)

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using

two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.

Model

Hz

Volts

Voltage range

FXFQ20~125

50

230

min. 198-max. 264

power supply

Fan motor

Model

MCA

MFA

KW

FLA

FXFQ20~50

0.5

16 A

0.045

0.4

FXFQ63

0.6

16 A

0.045

0.5

FXFQ80

1.0

16 A

0.090

0.8

FXFQ100

1.1

16 A

0.090

0.9

FXFQ125

1.4

16 A

0.090

1.1

NOTE

For details, refer to "Electrical data".

Power supply wiring

Model

Field fuses

Wire

Size

FXFQ20~125

16 A

H05VV-U3G

Local codes

Transmission wiring

Model

Wire

Size

FXFQ20~125

Sheathed wire (2)

0.75-1.25 mm

2

NOTE

For details, refer to the chapter "

Wiring example

".

Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:

Outdoor unit - indoor unit: max. 1000 m 
(total wiring length: 2000 m)

Indoor unit - remote controller: max 500 m

1

Switch box lid (1)

2

Power supply

3

Power supply terminal board

4

Rubber bush A

5

Clamp A

6

Switch box lid (2) with wiring diagram label

7

Transmission wiring

8

Terminal board for transmission wiring

9

Rubber bush B

10

Clamp B

11

Outside of the unit

12

Inside of the unit

13

Cable (power supply or transmission wiring)

14

Opening for the cable

15

Small sealing

Summary of Contents for FXFQ20M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20M8V3B FXFQ25M8V3B FXFQ32M8V3B FXFQ40M8V3B FXFQ50M8V3B FXFQ63M8V3B FXFQ80M8V3B FXFQ100M8V3B FXFQ125M8V3B System air conditioners...

Page 2: ...840 780 5 6 7 8 680 840 860 910 950 12 12 3 5 10 1 8 6 7 11 12 15 4 2 14 7 9 13 4 4 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 6 6 1 2 3 4 7 7 7 1 4 6 3 5 2 3 18 mm 8 8 5 75 550 750 220 300...

Page 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Page 4: ...sories are included with your unit Optional accessories There are two types of remote controllers wired and wireless Select a remote controller according to customers request and install in an appropr...

Page 5: ...ad kit and to the chapter Field setting See figure 1 air flow direction 4 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If t...

Page 6: ...equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four c...

Page 7: ...ng water See figure 13 When electric wiring work is finished Check drainage flow during COOL running explained in chapter Test operation When electric wiring work is not finished Remove the switch box...

Page 8: ...es Precautions 1 Observe the notes mentioned below when wiring to the power supply terminal board Do not connect wires of different gauge to the same power supply terminal Looseness in the connection...

Page 9: ...100 hrs 1 Long life filter type Change the setting when ultra long life filter is installed This setting is important for time between 2 filter cleaning display indications refer to 10 0 0X Long life...

Page 10: ...No 12 then set the first code switch No to 1 Then set second code position No to 01 for forced off and to 02 for on off operation forced off at factory set See figure 22 Centralized control For centr...

Page 11: ...or wash the air filter with water When the air filter is very dirty use a soft brush and neutral detergent Remove water and dry in the shade 4 Fix the air filter Attach the air filter to the suction...

Page 12: ...attach the suction grill See item No 2 5 Close the suction grill See item No 1 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in acco...

Page 13: ...DIODE SERVICE MONITOR RED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 S...

Page 14: ...NOTES NOTES...

Page 15: ...1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 20 20 S M S S M 2 3 1 17 17 18 18 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 16 16 L...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25082 1A...

Reviews: