background image

8

NOTE

• Apply ester oil or ether oil around the flare portions before 

connecting.

• The flare nuts used must be those included with the main 

body.

• Over-tightening may damage the flare and cause a refriger-

ant leakage.

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to 
install the unit without a torque wrench, you may
follow the installation method mentioned below.

After the work is finished, make sure to check that 
there is no gas leak.

When you keep on tightening the flare nut with a spanner, 
there is a point where the tightening torque 
suddenly increases. From that position, further tighten the 
flare nut the angle shown below:

Table 4

7-3

Piping insulation

• Execute heat insulation work completely on both sides of the 

gas piping and the liquid piping. Otherwise, a water leakage 
can result sometimes.

• When using a heat pump, the temperature of the gas piping 

can reach up to approximately 250°F, so use insulation 
which is sufficiently resistant.

• Also, in cases where the temperature and humidity of the refrig-

erant piping sections might exceed 86°F or RH80%, reinforce 
the refrigerant insulation. (13/16” or thicker) Condensation may 
form on the surface of the insulating material.

• Check the pipe connector for gas leaks, then insulate it as 

shown in the drawing below.

• Make absolutely sure to execute heat insulation works on the 

pipe-connecting section after checking gas leakage by thor-
oughly studying the following figure and using the attached 
heat insulating materials for fitting. (Fasten both ends with 
the clamps (accessory).)

• Wrap the sealing pad (accessory) only around the insulation 

for the joints on the gas piping side. 

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

7-4

Brazing referigerant piping

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 2.9psi. with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping.

NOTE

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filter metal (BCuP) which 
does not require flux.
(Flux has extremely harmful infulence on refrigerant piping 
sysems. For instance, if the chlorine based flux is used, it 
will cause pipe corrosion or, in particular, if the flux contains 
fluorine, it will damage the refrigerant oil.)

8. DRAIN PIPING WORK

〈〈

Rig the drain pipe as shown below and take measures 

against condensation.  Improperly rigged piping could lead 
to leaks and eventually wet furniture and belongings.

〉〉

(1) Rig drain piping

• The diameter of the drain pipe should be greater than or 

equal to the diameter of the connecting pipe (vinyl tube; pipe 
size: 1”; outer dimension: 1 1/4”). (This does not apply to 
rises.)

• Keep the drain pipe short and sloping downwards at a gradi-

ent of at least 1/100 to prevent air pockets from forming.

• If the drain hose cannot be sufficiently set on a slope, exe-

cute the drain raising piping.

• To keep the drain hose from sagging, space hanging wires 

every 3.28 ~ 4.92ft .

Pipe size

Further tightening 

angle

Recommended arm length of 

tool (in.)

φ 

1/4”

60 to 90 degrees

Approx. 5 7/8

φ 

3/8”

60 to 90 degrees

Approx. 7 7/8

φ 

1/2”

30 to 60 degrees

Approx. 9 13/16

φ 

5/8”

30 to 60 degrees

Approx. 11 13/16

Summary of Contents for FXFQ12MVJU

Page 1: ...VJU FXFQ18MVJU FXFQ24MVJU FXFQ30MVJU FXFQ36MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future...

Page 2: ...LATION 5 5 INSTALLATION PROCEDURES FOR FRESH AIR INTAKE DUCT CONNECTION 6 6 INDOOR UNIT INSTALLATION 6 7 REFRIGERANT PIPING WORK 7 8 DRAIN PIPING WORK 8 9 ELECTRIC WIRING WORK 10 10 WIRING EXAMPLE AND...

Page 3: ...esult in the equip ment falling and causing injuries Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Improper installation work may result in t...

Page 4: ...ne of transport Leave the unit inside its packaging while moving until reach ing the installation site Where unpacking is unavoidable use a sling of soft material or protective plates together with a...

Page 5: ...t be sufficient enough to eliminate the noise 2 Ceiling height This indoor unit may be installed on ceilings up to 11 5 ft 30 36 13 8 ft in height Refer to the table 3 Air flow direction The below fig...

Page 6: ...rked on the paper pattern for instal lation Refer to it to check for points requiring reinforcing length in 4 PREPARATIONS BEFORE INSTALLA TION 1 Relation of ceiling opening to unit and suspension bol...

Page 7: ...nd a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the ceiling before proceeding further 5 IN...

Page 8: ...BEFORE INSTALLATION 1 3 Perform steps 4 5 in 6 1 For new ceilings 7 REFRIGERANT PIPING WORK 7 1 GENERAL INSTRUCTIONS For refrigerant piping of outdoor units see the installation man ual attached to t...

Page 9: ...unit Any exposed piping may cause condensation or burns if touched 7 4 Brazing referigerant piping Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air...

Page 10: ...r the operating capacity of the unit NOTE Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit...

Page 11: ...ax 3280 ft Total wiring length 6560 ft 2 Indoor unit Remote controller Max 1640 ft 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER 10 1 HOW TO CONNECT WIRINGS Methods of wiring power supply uni...

Page 12: ...he terminal Tightening torque 0 97ft lbf 10 2 Tightening torque for the terminal screws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head...

Page 13: ...rystal display air filer signs to display the time to clean air filters Change the SECOND CODE NO according to Table 5 depending on the amount of dirt or dust in the room SECOND CODE NO is factory set...

Page 14: ...ON FOR SERVICING of the outdoor unit If any of the items in Table 6 are displayed there may be a problem with the wiring or power so check the wiring again Table 4 Remote control display Content Conce...

Page 15: ...14 MEMO...

Page 16: ...0403 HT 3PN01417 8U EM03A040B Daikin US Corporation 375 Park Avenue Suite 3308 New York NY 10152 www daikinac com info daikinac com...

Reviews: