9. ELECTRIC WIRING WORK 

9-1

GENERAL INSTRUCTIONS 

• All field supplied parts and materials, electric works must 

conform to local codes.

• Use copper wire only.
• Follow the “WIRING DIAGRAM” attached to the unitbody to 

wire the outdoor unit, indoor units and the remote controller.  
For details on hooking up the remote controller, refer to the 
“INSTALLATION MANUAL OF REMOTE CONTROLLER”.

• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units.  Mark each 

indoor unit as unit A, unit B . . . , and be sure the terminal 
board wiring to the outdoor unit and BS unit are properly 
matched.  If wiring and piping between the outdoor unit and 
an indoor unit are mismatched, the system may cause a mal-
function.

• A circuit breaker capable of shutting down the power supply 

to the entire system must be installed.

9-2

ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A)   MFA: Max. Fuse Amps (A) 
kW: Fan Motor Rated Output (W)   FLA: Full Load Amps (A)

9-3

SPECIFICATIONS FOR FIELD SUPPLIED 

FUSES AND WIRE 

Allowable length of transmission wirings and remote controller 
wiring are as follows.

(1) Outdoor unit – Indoor unit: 

Max. 3280 ft. (Total wiring length: 6560 ft.) 

(2) Indoor unit – Remote controller: 

Max. 1640 ft.

10. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER

10-1 HOW TO CONNECT WIRINGS 

Methods of wiring power supply, units and connecting remote 

controller wirings

• Power supply wiring

Remove the electric parts box lid (1) and connect wires to the 

power supply terminal block (3P) inside. In doing this, pull the 

wires inside through rubber bush A and clamp the wires 

along with other wires using clamp A, untightening the clip of 

clamp A by pressing. After the connection, tighten clamp A 

as before.

• Unit wiring and remote controller wiring

Remove the electric parts box lid (2) and pull the wires inside 

through rubber bush B and connect to the terminal block for 

unit transmission wirings (6P).

• After connection, attach sealing pad

(Be sure to attach it to prevent water from infiltrating the unit 

from the outside.)

Units

Power 
supply

Fan motor

Model

Hz Volts

Voltage 

range

MCA MFA

W

FLA

FXFQ12 MVJU

60

208-

230V

Max. 

253

Min.  187

0.6

15

45

0.5

FXFQ18 MVJU

0.7

15

45

0.6

FXFQ24MVJU

0.8

15

45

0.6

FXFQ30MVJU

1.2

15

90

1.0

FXFQ36MVJU

1.2

15

90

1.0

Model

Power supply wiring

Transmission 

wiring

Field fuses 

Size

Wire

Size

FXFQ12 MVJU

15A

Wire size 
must 
comply with 
local codes.

Sheathed wire 
(2 wire)

AWG

18-16

FXFQ18MVJU

FXFQ24MVJU

FXFQ30MVJU

FXFQ36MVJU

Summary of Contents for FXFQ12MVJU

Page 1: ...VJU FXFQ18MVJU FXFQ24MVJU FXFQ30MVJU FXFQ36MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future...

Page 2: ...LATION 5 5 INSTALLATION PROCEDURES FOR FRESH AIR INTAKE DUCT CONNECTION 6 6 INDOOR UNIT INSTALLATION 6 7 REFRIGERANT PIPING WORK 7 8 DRAIN PIPING WORK 8 9 ELECTRIC WIRING WORK 10 10 WIRING EXAMPLE AND...

Page 3: ...esult in the equip ment falling and causing injuries Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Improper installation work may result in t...

Page 4: ...ne of transport Leave the unit inside its packaging while moving until reach ing the installation site Where unpacking is unavoidable use a sling of soft material or protective plates together with a...

Page 5: ...t be sufficient enough to eliminate the noise 2 Ceiling height This indoor unit may be installed on ceilings up to 11 5 ft 30 36 13 8 ft in height Refer to the table 3 Air flow direction The below fig...

Page 6: ...rked on the paper pattern for instal lation Refer to it to check for points requiring reinforcing length in 4 PREPARATIONS BEFORE INSTALLA TION 1 Relation of ceiling opening to unit and suspension bol...

Page 7: ...nd a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the ceiling before proceeding further 5 IN...

Page 8: ...BEFORE INSTALLATION 1 3 Perform steps 4 5 in 6 1 For new ceilings 7 REFRIGERANT PIPING WORK 7 1 GENERAL INSTRUCTIONS For refrigerant piping of outdoor units see the installation man ual attached to t...

Page 9: ...unit Any exposed piping may cause condensation or burns if touched 7 4 Brazing referigerant piping Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air...

Page 10: ...r the operating capacity of the unit NOTE Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit...

Page 11: ...ax 3280 ft Total wiring length 6560 ft 2 Indoor unit Remote controller Max 1640 ft 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER 10 1 HOW TO CONNECT WIRINGS Methods of wiring power supply uni...

Page 12: ...he terminal Tightening torque 0 97ft lbf 10 2 Tightening torque for the terminal screws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head...

Page 13: ...rystal display air filer signs to display the time to clean air filters Change the SECOND CODE NO according to Table 5 depending on the amount of dirt or dust in the room SECOND CODE NO is factory set...

Page 14: ...ON FOR SERVICING of the outdoor unit If any of the items in Table 6 are displayed there may be a problem with the wiring or power so check the wiring again Table 4 Remote control display Content Conce...

Page 15: ...14 MEMO...

Page 16: ...0403 HT 3PN01417 8U EM03A040B Daikin US Corporation 375 Park Avenue Suite 3308 New York NY 10152 www daikinac com info daikinac com...

Reviews: