Installation
EDUS391000-F1
34
FXFQ-P
3P161684-5H
20
English
CAUTION
•
W
hen clamping wiring, use the included clamping material to prevent outside pressure being exerted on the
wiring connections and clamp firmly.
W
hen doing the wiring, make sure the wiring is neat and does not
cause the control box lid to stick up, then close the cover firmly.
•
W
hen attaching the control box lid, make sure you do not pinch any wires.
•
A
fter all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (pro-
cured locally) to prevent small animals and insects from entering the unit from outside. (If they get in, they
could cause short circuits in the control box.)
•
Outside the unit, separate the low voltage wiring (remote controller cord) and high voltage wiring (power
supply, ground, and other power wiring) at least 2in. so that they do not pass through the same place
together. Proximity may cause electrical interference, malfunctions, and breakage.
9-2 Wiring example
•
Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE (3 systems)
Remote controller wiring
Sealing pad (Small) (13)
Putty or thermal insulation material
(procured locally)
Wiring through-holes
Processing method of wiring through-holes
Power supply wiring
Transmission wiring
Switch
Fuse
"REAKER
Power supply
Main
switch
Remote controller
Indoor unit
B
RANCH
S
ELECTOR
unit
(Only for
Heat
recovery system)
Fig. 28
Note:
Field wiring diagram is to be used as a guideline only. Wiring should comply with
applicable local and national codes.