Installation
EDUS391000-F1
28
FXFQ-P
3P161684-5H
14
English
•
Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water leak-
age due to dew condensation.
•
Indoor drain pipe
•
Drain socket
<PRECAUTIONS FOR DRAIN
2)3%2
P
)0
ING>
•
Install the drain
ris
ER
pipes at a height of less than 26-1/2in..
The drain pump of this unit has a high delivery flow rate. Therefore, the higher the drain
r
ISER
height is, the
lower the sound of draining will be. For this reason, a minimum drain
ri
S
ing height of 12in. is recommended.
•
Install the drain
r
I
s
ER
ipes at a right angle to the indoor unit and no more than 11-3/4in. from the unit.
NOTE
•
To ensure no excessive pressure is applied to the included drain hose (1), do not bend or twist when install-
ing. (This may cause leakage.)
•
If converging multiple drain pipes, install according to the procedure shown below.
Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
(2)
After piping work is finished, check if drainage flows smoothly.
Metal
clamp (2)
Tape (White)
Drain hose (1)
Fig. 19
Metal
clamp (2)
Large sealing pad (10)
(accessory)
(accessory)
5/32in.
Fig. 20
≥
Ceiling slab
Metal clamp
(accessory) (2)
Drain hose (1)
(accessory)
Drain
ris
ER
pipe
Rising section
Drain hose (accessory) (1)
33-1/2in.
Hanger bracket
Adjustable
(
26-1/2in.)
3-5ft.
11-3/4in.
7in.
Fig. 21
≥
≥
≥
To prevent air bubbles in the
drain hose part, keep it level or
slightly tilted up. Any bubbles in
the hose might cause the unit
to make noise due to backflow
when the drain pump stops.
Level or
tilted
slightly up
0 – 26-1/2in.
Fig. 22
Water accumulating in the drain
piping can cause the drain to clog.
Central drain pipe
The drain pipe should have a downward
slope of at least 1/100 to prevent
air pockets from forming.