![background image](http://html1.mh-extra.com/html/daikin/fxfq-m/fxfq-m_engineering-data_2459698032.webp)
EDUS39-600-F1_a
Installation
FXFQ-M
31
11. WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER
11-1 HOW TO CONNECT WIRINGS
〈
Methods of wiring power supply, units and connecting
remote controller wirings
〉
• Power supply wiring: Remove the electric parts box lid (1)
and connect wires to the power supply terminal block (3P)
inside. In doing this, pull the wires inside through rubber
bush A and clamp the wires along with other wires using
clamp A, untightening the clip of clamp A by pressing. After
the connection, tighten clamp A as before.
• Unit wiring and remote controller wiring: Remove the elec-
tric parts box lid (2) and pull the wires inside through rubber
bush B and connect to the terminal block for unit transmis-
sion wirings (6P).
• After connection, attach sealing pad to prevent water from
infiltrating the unit from the outside.)
WARNING
• Never connect power supply wiring to the terminal block for
remote controller wiring as this could damage the entire
system.
• Use only specified wire and connect wires to the terminal
tightly. Be careful wires do not place external stress on ter-
minals. Keep wires in neat order so as to not obstruct other
equipment. Make sure that the electric box lid fits tightly.
Incomplete connections could result in overheating and, in
NOTE
worse case, result in electric shock or fire.
• To avoid a short circuit in the electric parts box, be sure to
apply sealing material or putty (not included) to the wiring
hole to prevent the infiltration of water as well as insects or
other small creatures.
• When clamping the wires, be sure no pressure is applied to
the wire connections by using the included clamping mate-
rial to make appropriate clamps. Also, when wiring, make
sure the lid on the electric parts box fits snugly by arranging
the wires neatly and attaching the electric parts box lid
firmly. When attaching the electric parts box lid, make sure
no wires get caught in the edges. Pass wiring through the
wiring through holes to prevent damage to them.
• Make sure the remote controller wiring, the wiring between
the units, and other electrical wiring do not pass through
the same locations outside of the unit, separating them by
at least 1 15/16”, otherwise electrical noise (external static)
could cause mistaken operation or breakage.
1. Use round crimp-style terminals for connecting wires
to the power supply terminal block.
If unavailable, observe the following points when wir-
ing.
• Do not connect wires of different gauge to the same
power supply terminal.
(Looseness in the connection may cause overheating.)
• Use the specified electric wire. Connect the wire
securely to the terminal. Lock the wire down without
applying excessive force to the terminal. (Tightening
torque: 0.97ft.lbf ±10 %)
Clamp A
Grounding
terminal
Power supply terminal
block (3P)
Electric parts box lid (1)
Electric wiring
diagram label
Electric parts box lid (2)
Terminal board
for transmission
wiring (6P)
Rubber
bush B
Rubber
bush A
Conduit
mounting
plate
Conduit
Lock nut
Rubber bush A
Rubber
bush
Wrap pad tightly enough
to prevent gapping.
Sealing pad (Small)
(Wrap around the wire)
(Inside)
(Outside)
Field wiring
〈
NOTES
〉
• If using 2 or more wires, break the small
sealing pad (Small) and wrap each wire.
Be sure to attach it to prevent the infiltration
of water as well as any insects and other
small creatures from outside.
Otherwise a short-circuit may occur inside
the electric parts box.
L1 L2
Clamp A
Clip
Power
supply
Power supply
terminal block (3P)
Electric wire
Round crimp-style terminal
Attach insulation sleeve
Connect wires of
the same gauge to
both sides.
Summary of Contents for FXFQ-M
Page 1: ...EDUS 39 600 F1_a AMERICAS FXFQ M Ceiling Mounted Cassette Type Multi Flow...
Page 3: ...External Appearance EDUS39 600 F1_a FXFQ M 2 1 External Appearance FXFQ12 36M...
Page 6: ...EDUS39 600 F1_a Dimensions FXFQ M 5 3 Dimensions FXFQ12MVJU FXFQ18MVJU 3D042631...
Page 7: ...Dimensions EDUS39 600 F1_a FXFQ M 6 FXFQ24MVJU 3D042632...
Page 8: ...EDUS39 600 F1_a Dimensions FXFQ M 7 FXFQ30MVJU FXFQ36MVJU 3D042633A...
Page 11: ...Electric Characteristics EDUS39 600 F1_a FXFQ M 10 6 Electric Characteristics...