Installation
EDUS39-600-F1_a
26
FXFQ-M
5.
INSTALLATION PROCEDURES FOR
FRESH AIR INTAKE DUCT CONNECTION
(1) Cut off the knockout hole on the side plate.
Then, cut the inner insulation of the hole portion.
Refer to Fig. 1
(2) Adhere the insulation to the opening of the unit.
Refer
to Fig. 2
6.
INDOOR UNIT INSTALLATION
Installing optional accessories (except for the decoration
panel) before installing the indoor unit is easier. However,
for existing ceilings, install fresh air inlet component kit
and branch duct before installing the unit.
(1) Install the indoor unit temporarily.
• Attach the hanger bracket to the suspension bolt. Be
sure to fix it securely by using a nut and washer from the
upper and lower sides of the hanger bracket.
The washer fixing plate ( 7) will prevent the washer from
falling.
6-1
For new ceilings
(1) Refer to the paper pattern for installation 5) for ceiling
opening dimension.
Consult the builder or carpenter for details.
• The center of the ceiling opening is indicated on the
paper pattern for installation.
The center of the unit is indicated on the label attached
to the unit and on the paper pattern for installation.
• After removing the packaging material from the 4 cor-
ners of the paper pattern for installation (5), fix the
paper pattern to the unit with the 4 screws (6).
• Ceiling height is shown on the side of the paper pattern
for installation (5). Adjust the height of the unit accord-
ing to this indication.
Drain pipe
Pipe
Side plate
Inner insulation
Inner
insulation
Slit
Side plate
Cut it off with cutter.
Cut it off with nipper
Fig. 1
Insulation
(field supply)
Put the insulation tightly around the hole of the unit
as shown. The ends of the side plate and the inner
insulation must be completely adhered without
leaving any clearance along the circumference of
the hole.
Inner insulation
Side plate
Edge
Insulation
Approx. 3/8”
Make sure the inner surface of insulation tightly contacts
with the inner insulation edge and the side plate.
Fig. 2
Part to be procured in the field
Washer 3) (attached)
Hanger bracket
Tighten
(double nut)
[Securing the hanger bracket]
Summary of Contents for FXFQ-M
Page 1: ...EDUS 39 600 F1_a AMERICAS FXFQ M Ceiling Mounted Cassette Type Multi Flow...
Page 3: ...External Appearance EDUS39 600 F1_a FXFQ M 2 1 External Appearance FXFQ12 36M...
Page 6: ...EDUS39 600 F1_a Dimensions FXFQ M 5 3 Dimensions FXFQ12MVJU FXFQ18MVJU 3D042631...
Page 7: ...Dimensions EDUS39 600 F1_a FXFQ M 6 FXFQ24MVJU 3D042632...
Page 8: ...EDUS39 600 F1_a Dimensions FXFQ M 7 FXFQ30MVJU FXFQ36MVJU 3D042633A...
Page 11: ...Electric Characteristics EDUS39 600 F1_a FXFQ M 10 6 Electric Characteristics...