EDUS39-600-F1_a
Installation
FXFQ-M
23
2-1
ACCESSORIES
Check the following accessories are included with your unit.
2-2
OPTIONAL ACCESSORIES
• The optional decoration panel and remote controller are
required for this indoor unit.
Table 1
Table 2
FOR THE FOLLOWING ITEMS, TAKE SPECIAL
CARE DURING CONSTRUCTION AND CHECK
AFTER INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
b. Items to be checked at time of delivery
Also review the
SAFETY CONSIDERATIONS
2-3
NOTE TO INSTALLER
• Be sure to instruct customers how to properly operate the
unit (especially cleaning filters, operating different functions,
and adjusting the temperature) by having them carry out
operations themselves while looking at the manual.
Name
1) Drain
hose
2) Metal
clamp
3) Washer for
hanger
bracket
4) Clamp
Quantity
1 pc.
1 pc.
8 pcs.
4 pcs.
Shape
Name
5) Paper
pattern for
installation
6) Screws
(M5)
7) Washer
fixing plate
Insulation for
fitting
Quantity
1 pc.
4 pcs.
4 pcs.
1 each
Shape
Also used as
packing
material
For paper
pattern for
installation
8) for gas
pipe
9) for liquid
pipe
Name
Sealing pad
(Other)
Installation manual
Operation manual
Quantity
1 each
2 pcs.
Shape
10) Large
11) Medium
12) Small
Model
Optional decoration panel
Color
White
FXFQ12 · 18 · 24 · 30 · 36MVJU
BYC125KW1
Remote controller
Wired type
BRC1D71
Items to be checked
If not properly done, what is
likely to occur.
Check
Are the indoor and outdoor
unit fixed firmly?
The units may drop, vibrate
or make noise.
Is the gas leak test fin-
ished?
It may result in insufficient
cooling.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow
smoothly?
Condensate water may drip.
Does the power supply volt-
age correspond to that
shown on the name plate?
The unit may malfunction or
the components burn out.
Are wiring and piping cor-
rect?
The unit may malfunction or
the components burn out.
Is the unit safely grounded?
Dangerous at electric leak-
age.
Is wiring size according to
specifications?
The unit may malfunction or
the components burn out.
Is something blocking the
air outlet or inlet of either
the indoor or outdoor units?
It may result in insufficient
cooling.
Are refrigerant piping length
and additional refrigerant
charge noted down?
The refrigerant charge in
the system is not clear.
Items to be checked
Check
Did you explain about operations while showing the opera-
tion manual to your customer?
Did you hand the operation manual over to your customer?
Summary of Contents for FXFQ-M
Page 1: ...EDUS 39 600 F1_a AMERICAS FXFQ M Ceiling Mounted Cassette Type Multi Flow...
Page 3: ...External Appearance EDUS39 600 F1_a FXFQ M 2 1 External Appearance FXFQ12 36M...
Page 6: ...EDUS39 600 F1_a Dimensions FXFQ M 5 3 Dimensions FXFQ12MVJU FXFQ18MVJU 3D042631...
Page 7: ...Dimensions EDUS39 600 F1_a FXFQ M 6 FXFQ24MVJU 3D042632...
Page 8: ...EDUS39 600 F1_a Dimensions FXFQ M 7 FXFQ30MVJU FXFQ36MVJU 3D042633A...
Page 11: ...Electric Characteristics EDUS39 600 F1_a FXFQ M 10 6 Electric Characteristics...