EDUS39-600-F1_a
Installation
FXFQ-M
25
4.
PREPARATIONS BEFORE INSTALLATION
(1) Relation of ceiling opening to unit and suspension
bolt position
Installation is possible when ceiling-opening dimensions
are as follows:
•
(2) Make the ceiling opening needed for installation
where applicable. (For existing ceilings)
• Refer to the paper pattern for ceiling opening dimen-
sions.
• Create the ceiling opening required for installation.
From the side of the opening to the casing outlet, imple-
ment the refrigerant, drain piping, and wiring for remote
controller (unnecessary if wireless ) and indoor-out-
door unit casing outlet. Refer to each PIPING or WIR-
ING section.
• After making an opening in the ceiling, it may be neces-
sary to reinforce ceiling beams to keep the ceiling level
and to prevent it from vibrating. Consult the builder for
details.
(3) Install the suspension bolts using either a W3/8” or
M10 size bolt.
Use a hole-in anchor for existing ceilings, and a sunken
insert, sunken anchor, or other new ceiling parts to rein-
force the ceiling to bear the weight of the unit. Adjust
clearance from the ceiling before proceeding further.
37 3/8 (Decoration panel)
34 5/8 (Ceiling opening)
33 1/16 (Indoor unit)
30 11/16 (Suspension bolt pitch)
26 3/4 (Suspension bolt pitch)
33 1/16 (Indoor unit)
34 5/8 (Ceiling opening)
37 3/8 (Decoration panel)
A
Suspension
bolt (×4)
Refrigerant
piping
False
ceiling
Hanger
bracket
[View as seen from A]
(5 7/8)
(length: in.)
Ceiling material
1 3/8 or less
1 3/8 or less
NOTE) Installation is possible with a ceiling dimension of
35 13/16 (marked with *). However, to achieve a ceiling-
panel overlapping dimension of 13/16, the spacing
between the ceiling and the unit should be
1 3/8 or less. If the spacing between ceiling and the unit
is over 1 3/8, attach false ceiling to part or recover
the ceiling.
(length: in.)
Ceiling slap
Anchor
Long nut or turn-buckle
Suspension bolt
False ceiling
1 15/16” ~
3 15/16”
NOTE) All the above parts are field supplied.
〈
Installation example
〉
Summary of Contents for FXFQ-M
Page 1: ...EDUS 39 600 F1_a AMERICAS FXFQ M Ceiling Mounted Cassette Type Multi Flow...
Page 3: ...External Appearance EDUS39 600 F1_a FXFQ M 2 1 External Appearance FXFQ12 36M...
Page 6: ...EDUS39 600 F1_a Dimensions FXFQ M 5 3 Dimensions FXFQ12MVJU FXFQ18MVJU 3D042631...
Page 7: ...Dimensions EDUS39 600 F1_a FXFQ M 6 FXFQ24MVJU 3D042632...
Page 8: ...EDUS39 600 F1_a Dimensions FXFQ M 7 FXFQ30MVJU FXFQ36MVJU 3D042633A...
Page 11: ...Electric Characteristics EDUS39 600 F1_a FXFQ M 10 6 Electric Characteristics...