7. DRAIN PIPING WORK

CAUTION

Make sure all water is out before making the duct connection.

(1) Install the drain piping.

Make sure the drain works properly.

The diameter of the drain piping should be greater than or
equal to the diameter of the connecting pipe (vinyl tube; pipe
size: 20 mm; outer dimension: 26 mm).
(not including the riser)

Keep the drain piping short and sloping downwards at a gra-
dient of at least 1/100 to prevent air pockets from forming.

(Refer to Fig. 10)

CAUTION

Water accumulating in the drain piping can cause the 
drain to clog.

To keep the drain piping from sagging, space hanging
bracket every 1 to 1.5 m.

Use the drain hose (2) and the metal clamp (1). Insert the
drain hose (2) fully into the drain socket and firmly tighten the 
metal clamp (1) with the upper part of the tape on the hose
end. Tighten the metal clamp (1) until the screw head is less
than 4 mm from the hose. 

(Refer to Fig. 11, 12)

The two areas below should be insulated because conden-
sation may form there causing water to leak.

Drain piping passing indoors

Drain socket

Referring to the figure below, insulate the metal clamp (1) 
and drain hose (2) using the included large sealing pad (5).

(Refer to Fig. 12)

PRECAUTIONS FOR DRAIN RAISING PIPE 

Make sure the drain raising pipe height is no higher than
600mm.

Place the drain raising pipe vertically and make sure it is no
further than 300mm from the unit.

 (Refer to Fig. 13)

PRECAUTIONS 

Drain piping connections

Do not connect the drain piping directly to sewage pipes that
smell of ammonia. The ammonia in the sewage might enter
the indoor unit through the drain piping and corrode the heat
exchanger.

Do not twist or bend the drain hose (2), so that excessive
force is not applied to it.
(This type of treatment may cause leaking.)

If you are using central drain piping, follow the procedure
outlined in figure 10.

Select central drain piping of proper size according to the
capacity of the connected unit.

(2) After piping work is finished, check that the drainage

flows smoothly, as described below.

CAUTION

The electric wiring work shall be performed by qualified elec-
tricians.

If workers not having the electrician qualification have per-
formed the electric wiring work, steps 3 to 7 shall be per-
formed after the 

TEST RUN

.

(with rubber cap)

Service drain hole 

Refrigerant pipes

Drain socket

Central drain piping 
(with a slope of at least 1/100)

600mm 

or less

Fig. 10

(accessory)

(accessory)

Metal clamp (1)

Large sealing 
pad (5)

≤4mm

(accessory)

(accessory)

Fig. 12

Fig. 11

Tape

Drain hose (2)

Metal clamp (1)

Locate the drain hose horizontally 
or with a little upward gradient.

If there is an air bank, noise may be generated 
as a result of a water backflow when the drain 
pump comes to a stop.

Horizontal or 
upward slope

Drain hose (2) (accessory)

Fig. 13

1 – 1.5m

(Field supply)

(600mm or less)

Adjustable range

Hanging bracket

300 mm or less

Ceiling slab

Drain hose (2) (accessory)

Metal clamp (1) (accessory)

Drain raising pipe

4PEN365593-1C.book  Page 7  Thursday, April 20, 2017  1:00 PM

Summary of Contents for FXDQ15P3VE

Page 1: ...INSTALLATION MANUAL FXDQ15P3VE FXDQ20P3VE FXDQ25P3VE FXDQ32P3VE FXDQ40P3VE FXDQ50P3VE FXDQ63P3VE System Inverter Air Conditioners 4PEN365593 1C book Page 1 Thursday April 20 2017 1 00 PM...

Page 2: ...por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acor...

Page 3: ...do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried ou...

Page 4: ...unavoid able use a sling of soft material or protective plates together with a rope when lifting to avoid damage or scratches to the unit When moving the unit at or after opening hold the unit by the...

Page 5: ...allation Check whether the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit To avoid contact with the fan one of th...

Page 6: ...prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anc...

Page 7: ...ion may form on the surface of the insulation if the temperature above the ceiling reaches 30 C or the humidity RH80 CAUTION Follow the points below Use a pipe cutter and flare suitable for the type o...

Page 8: ...phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluorine...

Page 9: ...fer to Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drai...

Page 10: ...tion area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use...

Page 11: ...s Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case o...

Page 12: ...power sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring...

Page 13: ...For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 18 1...

Page 14: ...or remote controller to achieve remote control See the 11 FIELD SETTING AND TEST RUN for details on operation 10 4 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No...

Page 15: ...tion man ual included with the wireless remote controller for details on how to make the settings 3 Perform a test run according to the outdoor unit s installation manual The operation lamp of the rem...

Page 16: ...GHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT EYESENSOR S T THE...

Page 17: ...4P365593 1C 2017 03 Copyright 2013 Daikin 4PEN365593 1C book Page 1 Thursday April 20 2017 1 00 PM...

Reviews: