No. 3 system When including BS unit

10-2 CONTROL BY 2 REMOTE CONTROLLERS (Con-

trolling 1 indoor unit by 2 remote controllers)

When using 2 remote controllers, one must be set to “MAIN”
and the other to “SUB”.

MAIN/SUB CHANGEOVER

(1) Insert a 

 screwdriver into the recess between the

upper and lower part of remote controller and, working
from the 2 positions, pry off the upper part (2 loca-
tions).

The remote controller PC board is attached to the upper
part of remote controller.

(2) Turn the MAIN/SUB changeover switch on one of the

two remote controller PC boards to “S”.

(Leave the switch of the other remote controller set to “M”.)

Wiring Method

 (See ‘‘9. ELECTRIC WIRING WORK’’)

(3) Remove the control box lid.

(4) Add remote controller 2 (SUB) to the terminal block for

remote controller (P

1

, P

2

) in the control box.

(There is no polarity.)

[ PRECAUTIONS ]

Crossover wiring is needed when using group control and
2 remote controllers at the same time.

Connect the indoor unit at the end of the crossover wire
(P

1

, P

2

) to remote controller 2 (SUB).

10-3 REMOTE CONTROL (FORCED OFF AND ON/

OFF OPERATION)

Connect input lines from the outside to the terminals T

1

and T

2

 on the terminal block (6P) for remote controller to

achieve remote control.

See the “

11. FIELD SETTING AND TEST RUN”

 for

details on operation.

10-4 CENTRALIZED CONTROL

For centralized control, it is necessary to designate the group 
No. For details, refer to the manual of each optional control-
lers for centralized control.

L

N

F

F

1

2

F

F

1

2

F

F

1

2

F

F

1

2

IN/D

IN/D

OUT/D

OUT/D

1

P

P

2

1

F

2

N

F

L

1

2

T T

1

P

2

P

Power supply 

single phase 

50Hz 220-240V 

or single phase 

60Hz 220V

Fig. 21

Remote controller

(option)

Indoor unit A

BS unit

Outdoor unit

Upper part of 
remote controller

Lower part of 
remote controller

Insert the screwdriver here and gently work off the 
upper part of remote controller.

Only one remote controller 
needs to be changed if 
factory settings have 
remained untouched.

(Factory setting)

S

M

S

S

M

Remote controller 
PC board

Wire specification

Sheathed vinyl cord or cable (2 wires)

Gauge

0.75 - 1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum applica-
ble load of 15 V DC, 1 mA.

FORCED

OFF

REMOTE
CONTRL

TRANSMISSION

WIRING

Remote 
controller 1 
(MAIN)

Remote 
controller 2 
(SUB)

Remote controller wiring 
terminal block

Remote controller 2 
(SUB)

Remote controller 1 
(MAIN)

Crossover wire (P

1

.P

2

)

Max. No. of 
indoor units

Indoor unit 2

Indoor unit 1

FORCED

OFF

REMOTE

CONTRL

TRANSMISSION

WIRING

Input A

4PEN365593-1C.book  Page 12  Thursday, April 20, 2017  1:00 PM

Summary of Contents for FXDQ15P3VE

Page 1: ...INSTALLATION MANUAL FXDQ15P3VE FXDQ20P3VE FXDQ25P3VE FXDQ32P3VE FXDQ40P3VE FXDQ50P3VE FXDQ63P3VE System Inverter Air Conditioners 4PEN365593 1C book Page 1 Thursday April 20 2017 1 00 PM...

Page 2: ...por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acor...

Page 3: ...do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried ou...

Page 4: ...unavoid able use a sling of soft material or protective plates together with a rope when lifting to avoid damage or scratches to the unit When moving the unit at or after opening hold the unit by the...

Page 5: ...allation Check whether the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit To avoid contact with the fan one of th...

Page 6: ...prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anc...

Page 7: ...ion may form on the surface of the insulation if the temperature above the ceiling reaches 30 C or the humidity RH80 CAUTION Follow the points below Use a pipe cutter and flare suitable for the type o...

Page 8: ...phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluorine...

Page 9: ...fer to Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drai...

Page 10: ...tion area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use...

Page 11: ...s Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case o...

Page 12: ...power sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring...

Page 13: ...For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 18 1...

Page 14: ...or remote controller to achieve remote control See the 11 FIELD SETTING AND TEST RUN for details on operation 10 4 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No...

Page 15: ...tion man ual included with the wireless remote controller for details on how to make the settings 3 Perform a test run according to the outdoor unit s installation manual The operation lamp of the rem...

Page 16: ...GHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT EYESENSOR S T THE...

Page 17: ...4P365593 1C 2017 03 Copyright 2013 Daikin 4PEN365593 1C book Page 1 Thursday April 20 2017 1 00 PM...

Reviews: