![Daikin FXDQ15P3VE Installation Manual Download Page 6](http://html1.mh-extra.com/html/daikin/fxdq15p3ve/fxdq15p3ve_installation-manual_2459681006.webp)
4
English
4. PREPARATIONS BEFORE INSTALLATION
(1) Confirm the positional relationship between the unit
and suspension bolts. (Refer to Fig. 2)
•
Install the inspection opening on the control box side where
maintenance and inspection of the control box and drain
pump are easy. Install the inspection opening also in the
lower part of the unit.
(length: mm)
(2) Make sure the range of the unit’s external static pres-
sure is not exceeded.
(See the technical documentation for the range of the
external static pressure setting.)
(3) Open the installation hole. (Pre-set ceilings)
•
Once the installation hole is opened in the ceiling where
the unit is to be installed, pass refrigerant piping, drain
piping, transmission wiring, and remote controller wiring
(It is not necessary if using a wireless remote controller)
to the unit’s piping and wiring holes.
See “
6. REFRIGERANT PIPING WORK
”, “
7. DRAIN
PIPING WORK
”, and “
10.
WIRING EXAMPLE
”.
•
After opening the ceiling hole, make sure ceiling is level if
needed. It might be necessary to reinforce the ceiling
frame to prevent shaking.
Consult an architect or carpenter for details.
(4) Install the suspension bolts.
(Use W3/8 to M10 suspension bolts.)
Use a hole-in-anchor for existing ceilings, and a sunken
insert, sunken anchor or other part to be procured in the
field to reinforce the ceiling to bearing the weight of the unit
for new ceiling.
(Refer to Fig. 3)
(5) In case of bottom suction
(1) Remove the chamber lid. (7 locations)
(2) Reattach the removed chamber lid in the orientation
shown in Fig. 4. (7 locations)
(3) Attach the air filter (accessory) in the manner shown in
the diagram.
The four holes which cannot be covered by the air filter
should be covered with commercially available tape.
Model
A
B
15-20-25-32 type
750
740
40-50 type
950
940
63 type
1150
1140
B
A
620
500
450×450
620
A
Drain pump
SERVICE SPACE
Fig. 2
Inspection door
(Ceiling opening)
Allow view
Control box
Air inlet
(length : mm)
Suspension
bolt pitch
Air outlet
Ceiling
(Inspection
opening size)
(Suspension bolt pitch)
Fig. 3
Ceiling slab
Indoor unit
Anchor bolt
Long nut or turn-buckle
Suspension bolt
Note: All the above parts are field supplied.
(1)
(2)
Chamber lid
Chamber lid
Air discharge
Air inlet
Air discharge
Fig. 4
Air inlet
4PEN365593-1C.book Page 4 Thursday, April 20, 2017 1:00 PM