background image

English

5

5. INDOOR UNIT INSTALLATION



As for the parts to be used for installation work, be sure to 

use the provided accessories and specified parts desig-
nated by our company.



(1) Install the indoor unit temporarily.

Attach the hanger bracket to the suspension bolt. Be sure 
to fix it securely by using a nut and washer from the upper 
and lower sides of the hanger bracket. 

(Refer to Fig. 5)

[ PRECAUTION ]

Since the unit uses a plastic drain pan, prevent welding 
spatter and other foreign substances from the air outlet  
during installation.

(2) Adjust the height of the unit.

(3) Check the unit is horizontally level.

CAUTION

• Make sure the unit is installed level using a level or a 

plastic tube filled with water. In using a plastic tube 
instead of a level, adjust the top surface of the unit to the 
surface of the water at both ends of the plastic tube and 
adjust the unit horizontally. (One thing to watch out for in 
particular is if the unit is installed so that the slope is not 
in the direction of the drain piping, this might cause leak-
ing.)

(4) Tighten the upper nut.

6. REFRIGERANT PIPING WORK

For refrigerant piping of outdoor units, see the installation 

manual attached to the outdoor unit.

Execute heat insulation work completely on both sides of 

the gas piping and the liquid piping. Otherwise, a water 
leakage can result sometimes.
Use insulation that can withstand temperatures of at least 
120°C. Reinforce the insulation on the refrigerant piping 
according to the installation environment. If the tempera-
ture above the ceiling might reach 30°C or the humidity 
RH80%. Condensation may form on the surface of the insu-
lation.

CAUTION

Follow the points at below.

Use a pipe cutter and flare suitable for the type of refrigerant.

Apply ester oil or ether oil to the flare section when using a 
flare connection.

Only use the flare nuts included with the unit. Using different 
flare nuts may cause the refrigerant to leak.

To prevent dust, moisture or other foreign matter from infil-
trating the piping, either pinch the end or cover it with tape.

Do not allow anything other than the designated refrigerant 
to get mixed into the refrigerant circuit, such as air, etc. If any 
refrigerant gas leaks while working on the unit, ventilate the 
room thoroughly right away.

(1) Connect the piping.

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together, 
as shown in the drawing, when connecting or disconnecting 
pipes to/from the unit. 

(Refer to Fig. 6)

Refer to the Table 1 for the dimensions of flare nut spaces.

Apply ester oil or ether oil to flare section (both inside and 
out) when using flare nut connections and then turn 3 or 4 
times by hand. 

(Refer to Fig. 7)

(3)

Attach the filter to the 
main unit while pushing 
down on the bends.

Main unit

Force

Force

Filter

In case of back side

In case of bottom side

(accessory)

(accessory)

Washer fixing plate (11)

Insert below washer

Fig. 5

Tighten
(double nut)

Hanger 
bracket

Washer for 
hanging bracket (8)

[ How to secure washers ]

[ Securing the hanger bracket ]

Part to be procured 
in the field

Level

Vinyl tube

Fig. 7

Fig. 6

Flare nut

Piping union

Ester oil or ether oil

Spanner

Torque wrench

Summary of Contents for FXDQ15A2VEB

Page 1: ...INSTALLATION MANUAL FXDQ15A2VEB FXDQ20A2VEB FXDQ25A2VEB FXDQ32A2VEB FXDQ40A2VEB FXDQ50A2VEB FXDQ63A2VEB System Inverter Air Conditioners...

Page 2: ...es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o par...

Page 3: ...n work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power sup...

Page 4: ...ng hold the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit U...

Page 5: ...be shortened Indoor units should be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weig...

Page 6: ...inforce the ceiling frame to prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings an...

Page 7: ...ion environment If the tempera ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter...

Page 8: ...the refrigerant pipe joints Use phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a...

Page 9: ...300mm from the unit Refer to Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoo...

Page 10: ...ide flange and duct connection area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air pass...

Page 11: ...to use insulated terminals Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOT...

Page 12: ...circumstances connect the power sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wir...

Page 13: ...ler for 1 indoor unit No 2 system For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply...

Page 14: ...LECTRIC WIRING WORK 3 Remove the control box lid 4 Add remote controller 2 SUB to the terminal block for remote controller P1 P2 in the control box There is no polarity L N F F1 2 F F1 2 F F1 2 F F1 2...

Page 15: ...OFF operation should be selected by selecting the SECOND CODE NO as shown in the table below The SECOND CODE NO is set to 01 when shipped Input A of forced off and ON OFF operation work as shown in th...

Page 16: ...If the display shows any of the following there is a possi bility that the wiring was done incorrectly or that the power is not on so check again CAUTION Always stop the test run using the remote con...

Page 17: ...NNECTOR FOR OPTIONAL PARTS X24A CONNECTOR WIRELESSREMOTE CONTROLLER X33A CONNECTOR ADAPTOR FOR WIRING X35A CONNECTOR POWER SUPPLY CONNECTOR X38A CONNECTOR MULTI TENANT WIRED REMOTE CONTROLLER R1T THER...

Page 18: ......

Page 19: ......

Page 20: ...4P325876 1 2012 07 Copyright 2012 Daikin...

Reviews: