10. WIRING EXAMPLE

10-1 HOW TO CONNECT WIRINGS 

Wire only after removing the control box lid as shown in 

Fig. 17, refering to view A.

CAUTION

Be sure to attach power supply wiring and earth wire to the 

control box with the clamp.

When doing the wiring, make sure the wiring is neat and 

does not cause the control box lid to stick up, then close the 

cover firmly. When attaching the control box lid, make sure 

you do not pinch any wires.

Outside the air conditioners, separate the weak wiring 
(remote controller and transmission wiring) and strong wiring 
(earth wire and power supply wiring) at least 50 mm so that 
they do not pass through the same place together. Proximity 
may cause electrical interference, malfunctions, and break-
age.

A main switch or other means for disconnection, having a 

contact separation in all poles, must be incorporated in the 

fixed wiring in accordance with relevant local and national 

legislation.

Note that the operation will restart automatically if the main 

power supply is turned off and then turned back on again.

[ PRECAUTIONS ] 

Refer to the “REMOTE CONTROLLER INSTALLATION 

MANUAL” on how to install and lay the wiring for the remote 

controller.

See also the “Wiring Diagram plate” attached to the control 

box lid when laying electrical wiring.

Connect the remote controller and transmission wiring their 

respective terminal blocks.

CAUTION

• Do not, under any circumstances, connect the power sup-

ply wiring to the remote controller or transmission wiring 

terminal block. Doing so can destroy the entire system.

[ Connecting electrical wiring, remote controller wiring, 
and transmission wiring ] (Refer to Fig. 18)

• Power supply and Earth wiring

Remove the control box lid.

Next, pull the wires into the unit through the wiring through 

hole and connect to the terminal block (3P).

Be sure to put the part of the sheathed vinyl into the control 

box.

(Rear)

Wiring Diagram

Control box lid

Power supply wiring
Earth wire

Penetration area

• Make sure to let a wire go through a wire penetration area.
• After wiring, seal the wire and wire penetration area to prevent 

moisture and small creatures from the outside.

• Wrap the strong and weak electric lines with the sealing 

material (12) as shown in the figure below.

  (Otherwise, moisture or small creatures such as insects from 

the outside may cause short-circuit inside the control box.) 
Attach securely so that there are no gaps.

Sealing 
material (12)

(accessory)

Wire

[How to adhere it]

Outside 
unit

Inside 
unit

Fig. 17

view A

Power supply wiring
Earth wire

Indoor PCboard 

(ASSY)

Clamps
(for preventing slippage)

*Transmission wiring
*Remote controller wiring

* Do not connect power 

supply wiring here.
That may cause 
malfunction

Control box

Control box

Power supply wiring/Earth wire

Fig. 18

Remote controller wiring
Transmission wiring

Power supply wiring
Earth wire

Wiring through hole

Wiring through hole

Terminal block (6P)

Terminal block (3P)

Indoor PCboard (ASSY)

Clamps

P1 P2 F1 F2 T1 T2

TRANSMISSION

    WIRING

FORCED

  OFF

REMOTE

 CNTRL

Summary of Contents for FXDQ15A2VEB

Page 1: ...INSTALLATION MANUAL FXDQ15A2VEB FXDQ20A2VEB FXDQ25A2VEB FXDQ32A2VEB FXDQ40A2VEB FXDQ50A2VEB FXDQ63A2VEB System Inverter Air Conditioners...

Page 2: ...es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o par...

Page 3: ...n work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power sup...

Page 4: ...ng hold the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit U...

Page 5: ...be shortened Indoor units should be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weig...

Page 6: ...inforce the ceiling frame to prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings an...

Page 7: ...ion environment If the tempera ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter...

Page 8: ...the refrigerant pipe joints Use phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a...

Page 9: ...300mm from the unit Refer to Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoo...

Page 10: ...ide flange and duct connection area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air pass...

Page 11: ...to use insulated terminals Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOT...

Page 12: ...circumstances connect the power sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wir...

Page 13: ...ler for 1 indoor unit No 2 system For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply...

Page 14: ...LECTRIC WIRING WORK 3 Remove the control box lid 4 Add remote controller 2 SUB to the terminal block for remote controller P1 P2 in the control box There is no polarity L N F F1 2 F F1 2 F F1 2 F F1 2...

Page 15: ...OFF operation should be selected by selecting the SECOND CODE NO as shown in the table below The SECOND CODE NO is set to 01 when shipped Input A of forced off and ON OFF operation work as shown in th...

Page 16: ...If the display shows any of the following there is a possi bility that the wiring was done incorrectly or that the power is not on so check again CAUTION Always stop the test run using the remote con...

Page 17: ...NNECTOR FOR OPTIONAL PARTS X24A CONNECTOR WIRELESSREMOTE CONTROLLER X33A CONNECTOR ADAPTOR FOR WIRING X35A CONNECTOR POWER SUPPLY CONNECTOR X38A CONNECTOR MULTI TENANT WIRED REMOTE CONTROLLER R1T THER...

Page 18: ......

Page 19: ......

Page 20: ...4P325876 1 2012 07 Copyright 2012 Daikin...

Reviews: