4. PREPARATIONS BEFORE INSTALLATION

(1) Confirm the positional relationship between the unit 

and suspension bolts. (Refer to Fig. 2)

Install the inspection opening on the control box side where 
maintenance and inspection of the control box and drain 
pump are easy.  Install the inspection opening also in the 
lower part of the unit.

(length: mm)

(2) Make sure the range of the unit’s external static pres-

sure is not exceeded.

(See the technical documentation for the range of the 
external static pressure setting.)

(3) Open the installation hole. (Pre-set ceilings)

Once the installation hole is opened in the ceiling where 

the unit is to be installed, pass refrigerant piping, drain 

piping, transmission wiring, and remote controller wiring 

(It is not necessary if using a wireless remote controller) 

to the unit’s piping and wiring holes.

See “

6. REFRIGERANT PIPING WORK

”, “

7. DRAIN 

PIPING WORK

”, and “

10.

 

WIRING EXAMPLE

”.

After opening the ceiling hole, make sure ceiling is level if 

needed. It might be necessary to reinforce the ceiling 

frame to prevent shaking.

Consult an architect or carpenter for details.

(4) Install the suspension bolts. 

(Use W3/8 to M10 suspension bolts.)

Use a hole-in-anchor for existing ceilings, and a sunken 

insert, sunken anchor or other part to be procured in the 

field to reinforce the ceiling to bearing the weight of the unit 

for new ceiling. 

(Refer to Fig. 3)

(5) In case of bottom suction

(1) Remove the chamber lid. (7 locations)

(2) Reattached the removed chamber lid in the orientation 

shown in Fig. 4. (7 locations)

(3) Attach the air filter (accessory) in the manner shown in 

the diagram.

The four holes which cannot be covered by the air filter 

should be covered with commercially available tape.

 

Model

A

B

15-20-25-32  type

750

740

40-50  type

950

940

63  type

1150

1140

B

A

620

500

450×450

620

A

Drain pump

SERVICE SPACE

Fig. 2

Inspection door

(Ceiling opening)

Allow view 

Control box

Air inlet

(length : mm)

Suspension 
bolt pitch

Air outlet

Ceiling

(Inspection 

opening size)

(Suspension bolt pitch)

Fig. 3

Ceiling slab

Indoor unit

Anchor bolt

Long nut or turn-buckle

Suspension bolt

Note: All the above parts are field supplied.

(1)

(2)

Chamber lid

Chamber lid

Air discharge

Air inlet

Air discharge

Fig. 4

Air inlet

Summary of Contents for FXDQ15A2VEB

Page 1: ...INSTALLATION MANUAL FXDQ15A2VEB FXDQ20A2VEB FXDQ25A2VEB FXDQ32A2VEB FXDQ40A2VEB FXDQ50A2VEB FXDQ63A2VEB System Inverter Air Conditioners...

Page 2: ...es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o par...

Page 3: ...n work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power sup...

Page 4: ...ng hold the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit U...

Page 5: ...be shortened Indoor units should be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weig...

Page 6: ...inforce the ceiling frame to prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings an...

Page 7: ...ion environment If the tempera ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter...

Page 8: ...the refrigerant pipe joints Use phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a...

Page 9: ...300mm from the unit Refer to Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoo...

Page 10: ...ide flange and duct connection area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air pass...

Page 11: ...to use insulated terminals Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOT...

Page 12: ...circumstances connect the power sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wir...

Page 13: ...ler for 1 indoor unit No 2 system For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply...

Page 14: ...LECTRIC WIRING WORK 3 Remove the control box lid 4 Add remote controller 2 SUB to the terminal block for remote controller P1 P2 in the control box There is no polarity L N F F1 2 F F1 2 F F1 2 F F1 2...

Page 15: ...OFF operation should be selected by selecting the SECOND CODE NO as shown in the table below The SECOND CODE NO is set to 01 when shipped Input A of forced off and ON OFF operation work as shown in th...

Page 16: ...If the display shows any of the following there is a possi bility that the wiring was done incorrectly or that the power is not on so check again CAUTION Always stop the test run using the remote con...

Page 17: ...NNECTOR FOR OPTIONAL PARTS X24A CONNECTOR WIRELESSREMOTE CONTROLLER X33A CONNECTOR ADAPTOR FOR WIRING X35A CONNECTOR POWER SUPPLY CONNECTOR X38A CONNECTOR MULTI TENANT WIRED REMOTE CONTROLLER R1T THER...

Page 18: ......

Page 19: ......

Page 20: ...4P325876 1 2012 07 Copyright 2012 Daikin...

Reviews: