background image

6

English

To prevent contamination or moisture from getting 
into the piping, take measures such as pinching or 
taping the pipings.

Do not mix substance other than the specified refriger-
ant such as air into the refrigeration circuit.
If the refrigerant leaks during the work, ventilate the 
room.

• The refrigerant is pre-charged in the outdoor unit.
• When connecting the pipings to the air conditioner, make 

sure to use a spanner and a torque wrench as shown in 

Fig. 1

.

• For the dimension of flared part and the tightening torque, 

refer to the Table 3.

• When making a flare connection, coat the flared inner sur-

face only with ether oil or ester oil. 

(Refer to Fig. 2)

Then, turn the flare nut 3 to 4 times with your hand and screw 
in the nut.

• Refer to Table 3 for tightening torque.

Table 3

NOTE

The flare nuts used must be those included with the main body.

CAUTION

Over-tightening may damage the flare and cause a refriger-
ant leakage.

Use “ Table 4 ” as a reference if a torque wrench is not available. 
Once work is complete, make sure there is no gas leaking. As 
the flare nut is tightened with the wrench, the torque will sud-
denly increase. 
From that position, tighten the nut to the angle shown on “ Table 4 ”.

• Make absolutely sure to execute heat insulation works on the 

pipe-connecting section after checking gas leakage by thor-
oughly studying the following figure and using the attached 
heat insulating materials for fitting. (Fasten both ends with 
the clamps (accessory).) 

(Refer to Fig. 3)

• Wrap the sealing pad (accessory) only around the insulation 

for the joints on the gas piping side. 

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-
ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filler metal (BCuP-2: JIS Z 
3264/B-Cu93P-710/795: ISO 3677) which does not require 
flux.
(Flux has extremely harmful influence on refrigerant piping 
systems. For instance, if the chlorine based flux is used, it will 
cause pipe corrosion or, in particular, if the flux contains flu-
orine, it will damage the refrigerant oil.)

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 0.02 MPa with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping.

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to install 
the unit without a torque wrench, you may follow the installa-
tion method mentioned below.

After the work is finished, make sure to check that there 
is no gas leak.

When you keep on tightening the flare nut with a spanner, 
there is a point where the tightening torque suddenly 
increases. From that position, further tighten the flare nut the 
angle shown below:

Pipe 

gauge

Tightening torque

(N·m)

Flare 

dimension A 

(mm)

Flare shape

 6.4

(1/4”)

15.7 ± 1.5

8.9 ± 0.2

 9.5

(3/8”)

36.3 ± 3.6

13.0 ± 0.2

 12.7

(1/2”)

54.9 ± 5.4

16.4 ± 0.2

 15.9

(5/8”)

68.6 ± 6.8

19.5 ± 0.2

A

45

0

± 2

0

R0.4-0.8

90

0

± 2

0

 

Coat the flared inner surface only with 
ether oil or ester oil.

Fig. 1

Torque wrench

Spanner

Piping union

Flare nut

Fig. 2

Insulation for 

fi

tting 

(accessory)

Small sealing pad

Insulation for 

fi

tting 

(accessory)

(for gas line)

Clamp (×4)

(accessory)

(for liquid line)

Liquid pipe

Fig. 3

(accessory)

Gas pipe

Refrigerant 
piping

Part to be 
brazed

Taping

Pressure-
reducing 
valve

hands valve

Nitrogen

Nitrogen

01_EN_3P258319-5K.fm  Page 6  Thursday, October 15, 2015  11:03 AM

Summary of Contents for FXCQ20MVE

Page 1: ...AUF VEUILLEZ LIRE ATTENTIVEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVEZ CE MANUEL EN LIEU S R POUR POUVOIR VOUS Y REPORTER ULT RI EUREMENT LEA DETENIDAMENTE ESTAS INSTRUCCIONES ANTES DE LA IN...

Page 2: ...FXHQ63MVE FXHQ100MVE FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50...

Page 3: ...electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition i...

Page 4: ...or protective plates together with a rope when lifting to avoid damage or scratches to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to t...

Page 5: ...llowable limit Refer to the installation manual for the outdoor unit Any vents light fixtures or other appliances which may disturb the airflow might cause the top side to become dirty if located too...

Page 6: ...3 Install the suspension bolts Use either a W3 8 or M10 size bolt Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field for new ceilin...

Page 7: ...m steps 3 4 5 in For new ceilings 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to the outdoor unit Carry out insulation of both gas and l...

Page 8: ...g Therefore use the phosphor copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For i...

Page 9: ...RECAUTIONS FOR DRAIN RAISING PIPING Install the drain raising pipes at a height of less than 310 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the...

Page 10: ...he entire system must be installed Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker a...

Page 11: ...arry out soldering finish when stranded wires are used Otherwise the loosening of wires may result in abnor mal heat radiation Abnormal heating may occur if the wirings are not tightened securely Use...

Page 12: ...the upper part The remote controller PC board is attached to the upper part of remote controller Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor...

Page 13: ...door units or to check the setting use the mode Nos with 2 in upper digit in parentheses Set the remote controller to the field set mode For details refer to the HOW TO SET IN THE FIELD in the remote...

Page 14: ...1511 HT 3P258319 5K EM02A084C...

Reviews: