Fan Speed Control for Indoor Unit
Outline
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature.
Automatic Fan
Speed Control
In automatic fan speed operation, the step SL is not available.
= The airflow rate is automatically controlled within this range when the
FAN
button is set to
automatic.
Cooling
The following drawing explains the principle of fan speed control for cooling.
*The upper limit is M tap for 30 minutes from the operation start.
Heating
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
Note:
The fan stops during defrost control.
COMFORT
AIRFLOW
Operation
FTX Series
The fan speed is controlled automatically within the following steps.
Cooling
L tap ~ MH tap (same as automatic)
Heating
L tap ~ M tap
The latest command has the priority between POWERFUL and COMFORT AIRFLOW.
Step
Cooling
Heating
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
(R11681)
(R6834)
(R21654)
Fan speed
+2.5°C (+4.5°F)
+1.5°C (+2.7°F)
+0.5°C (+0.9°F)
MH*
M
ML
L
+3°C (+5.4°F)
+2°C (+3.6°F)
+1°C (+1.8°F)
Room thermistor temperature – target temperature
Summary of Contents for FVXS09NVJU
Page 12: ...SiUS091601E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 15: ...SiUS091601E Specifications 4 Part 2 Specifications 1 Specifications 5 ...
Page 65: ...SiUS091601E Remote Controller 54 Part 5 Remote Controller 1 FTX Series 55 2 FVXS Series 57 ...
Page 144: ...Revision History Month Year Version Revised contents 02 2016 SiUS091601E First edition ...