![background image](http://html1.mh-extra.com/html/daikin/fvq71bv/fvq71bv_installation-manual_4703920007.webp)
English
5
3. SELECTING INSTALLATION SITE
Select an installation site where the following conditions are satisfied after obtaining your customer’s
approval.
• Where optimum air distribution can be ensured.
• Where nothing blocks the air inlet and outlet, and
where sufficient clearance for maintenance and
service can be ensured.
• Where condensate can be properly drained.
• Where the floor is strong enough to bear the indoor
unit weight.
• Make sure that the floor is not remarkably tilted.
• Where there is no risk of flammable gas leakage.
• Where piping between indoor and outdoor units is
possible within the allowable limit. (Refer to the
installation manual for the outdoor unit.)
• Keep indoor unit, outdoor unit, power supply wiring
and transmission wiring at least 1 meter away from
televisions and radio receivers. This is to prevent
image interference and noise in those electrical
appliances.
(Noise may be generated depending on the
conditions under which the electric wave is generated, even if 1 meter is kept.)
4. INDOOR UNIT INSTALLATION
As for the parts to be used for installation work, be sure to use the provided accessories and specified parts
designated by our company.
〈
Fixing procedure
〉
• Fix the indoor unit by using embedded bolt, etc. to prevent falling down of the vertically-long shaped unit.
1. Detach the air intake grille.
Remove the screws (R & L, total 2) locking the grille stopper. Then, (1) lean the grille forward you, and
(2) lift upward and out.
50mm
or more
50mm
or more
(1)
(2)
M4 × 12
Front panel
Grille
stopper
Air intake
grille
Screw
01_EN_3PA60136-8Y.fm Page 5 Saturday, December 22, 2007 1:04 PM