3. For normal installation.
Remove the screw (2) fixing the bracket for installation (1) to the top panel. Change the mounting
direction of the bracket as shown in the figure below and fix it to the top panel with the attached screws
(12). Then, fix the bracket to the wall with the appropriate screws (field supply).
•
Screws (2) are not used.
4. When installing the unit to a place where strength to earthquake is required.
In addition to the fixing method shown left, fix the bottom frame to the foundation with the anchor bolts
(field supply). Four holes for anchor bolts are prepared on the bottom plate.
•
Use the locations indicated on the installation pattern (9) (part of packing material).
5. Remove the cushion materials of the fan.
It may cause malfunction when operating while installed the cushion materials of the fan. (4 places)
Fixing screw
Screw (2) (accessory)
not necessary
Screw (12) (accessory)
Bracket for installation (1) (accessory)
2-7 × 15 slot
(accessory)
330
18
Bracket for
installation (1)
(Screw hole for
securing to the
wall) Prepare the
screws that match
the wall material as
field supply.
Fig. 5
• Unit [mm]
Fixing holes (× 4)
Bottom frame
(For locking with bolt)
4 -
φ
14 hole, Depth: 30
260
130
57
(79)
144