English
33
13. OPERATION RANGE
If the temperature or the humidity is beyond the following conditions, safety devices may work and the air
conditioner may not operate, or sometimes, water may drop from the indoor unit.
For combination with R410A outdoor unit, refer to the following table:
For combination with R32 outdoor unit, refer to the following table:
(a)
To avoid condensation and water dripping out of the unit. If the temperature or the humidity is beyond these
conditions, safety devices may be put in action and the air conditioner may not operate.
Outdoor units
Cooling
Heating
RZQG71~140
Outdoor
temperature
-15~50°C DB
-19~21°C DB
-20~15.5°C WB
Indoor
temperature
18~37°C DB
12~28°C WB
10~27°C DB
RZQSG71~140
Outdoor
temperature
-15~46°C DB
-14~21°C DB
-15~15.5°C WB
Indoor
temperature
20~37°C DB
14~28°C WB
10~27°C DB
RZQ200~250
Outdoor
temperature
-5~46°C DB
-14~21°C DB
-15~15°C WB
Indoor
temperature
20~37°C DB
14~28°C WB
10~27°C DB
AZQS125
(AVA125 model only)
Outdoor
temperature
-5~46°C DB
-15~15.5°C WB
Indoor
temperature
14~28°C WB
10~27°C DB
Indoor humidity
≤
80%
(a)
Outdoor units
Cooling
Heating
RZAG71~140
Outdoor
temperature
-20~52°C DB
-19.5~21°C DB
-20~15.5°C WB
Indoor
temperature
18~37°C DB
12~28°C WB
10~27°C DB
RZASG71~140
Outdoor
temperature
-15~46°C DB
-14~21°C DB
-15~15.5°C WB
Indoor
temperature
20~37°C DB
14~28°C WB
10~27°C DB
AZAS125
(AVA125 model only)
Outdoor
temperature
-5~46°C DB
-15~15°C WB
Indoor
temperature
14~28°C WB
10~27°C DB
Indoor humidity
≤
80%
(a)
3PEN486970-1D.book Page 33 Monday, July 24, 2017 8:54 AM