4. INDOOR UNIT INSTALLATION
WARNING
• Only use accessories, optional equipment and spare parts made or approved by DAIKIN.
• Installation shall be done by an installer, the choice of materials and installation shall comply with the
applicable legislation.
In Europe, the EN378 is the applicable standard that shall be used.
‹Fixing procedure›
• Since the indoor unit is vertically tall, take measures to prevent the unit from falling down according to the
following method.
1. Raise the grille fixture.
2. Detach the suction grille.
Remove the screws (R & L, total 2) locking the grille stopper. Then, (1) tilt the grille forward, and (2) lift upward.
Installation requirements for R32 units
250.00
200.00
150.00
100.00
50.00
0.00
1.84 1.94 2.04 2.14 2.24 2.34 2.44 2.54 2.64 2.74 2.84 2.94 3.04 3.14 3.24 3.34 3.44 3.54 3.64 3.74 3.84 3.94 4.04 4.14 4.24 4.34 4.44 4.54 4.64 4.74 4.84 4.94 5.04 5.14 5.24 5.34
Minimum floor area [m
2
]
Mass of refrigerant [kg]
Grille fixture
Fig. 3
Fig. 4
Front panel
Grille stopper
M4 × 12
Tapping screws (class 2)
Grille fixture
Suction grille
(1)
(2)