background image

3

English

2. Items to be checked at time of delivery

Also review the “SAFETY PRECAUTIONS”

Points for explanation about operations

2-4 NOTE TO THE INSTALLER

Be sure to instruct customers how to properly operate the unit 
(especially cleaning filters, operating different functions, and 
adjusting the temperature) by having them carry out operations 
themselves while looking at the manual.

3.

SELECTING INSTALLATION SITE 
AND AIR FLOW DIRECTION

3-1 Select an installation site where the following 

conditions are fulfilled and that meets your 
customer’s approval.

• In the upper space (including the back of the ceiling) of the 

indoor unit where there is no possible dripping of water 
from the refrigerant pipe, drain pipe, water pipe, etc.

• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• Where the ceiling is strong enough to bear the indoor 

unit weight.

• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service 

can be ensured.

• Where there is no risk of flammable gas leakage.
• Where piping between indoor and outdoor units is pos-

sible within the allowable limit. 
(Refer to the installation manual for the outdoor unit.)

[CAUTION]

Only use the included parts or parts which match the speci-
fications when installing the unit.

• Install the indoor unit no less than 2.5m above the floor. 

Where unavoidably lower, take what measures are nec-
essary to keep hands out of the air outlet.

** Space is required to attach/detach corner covers.

3-2 Air flow direction

Select the air flow direction that best suits the unit’s location. 2-
way and 3-way air flow must be set from the remote controller. 
For details, see FIELD SETTING.

NOTE

• Restrictions are placed on piping direction, therefore select 

flow direction from the below patterns.

[Air flow patterns] (Refer to Fig. 1)

(IIlustrations seen from ceiling)
A, B, C and D indicate drain pans.

Refrigerant pipe direction

To the rear (Straight pipe)

To the right (Elbow required)

Upward running refrigerant pipes are possible in all patterns.

3-3 Use suspension bolts for installation. Check 

whether the ceiling is strong enough to support 
the weight of the unit or not. If there is a risk, 
reinforce the ceiling before installing the unit.

(Installation pitch is marked on the paper pattern for 
installation. Refer to it to check for points requiring rein-
forcing.)

Is wiring size according 
to specifications?

The unit may malfunction 
or the components burn 
out.

Is something blocking 
the air outlet or inlet of 
either the indoor or out-
door units?

It may result in insuffi-
cient cooling.

Are refrigerant piping 
length and additional 
refrigerant charge noted 
down?

The refrigerant charge in 
the system is not clear.

Items to be checked

Check

Did you explain about operations while showing the 
instruction manual to your customer?

Did you hand the instruction manual over to your 
customer?

The items with 

WARNING and 

CAUTION marks in 

the instruction manual are the items pertaining to possi-
bilities for bodily injury and material damage in addition 
to the general usage of the product. Accordingly, it is 
necessary that you make a full explanation about the 
described contents and also ask your customers to read 
the instruction manual.

Space required for installation

≥ 

1500

≥ 

1000

≥ 

2500

≥ 

1500

≥ 

30

∗∗

≥ 

1000

Air discharge

F

or installation 

in high places

.

Air inlet

Obstruction

Floor

Floor

Air inlet

Obstruction

Air 
discharge

Air discharge

≥ 

1500

≥ 

2500

Air flow 
direction

Fig. 1

4-way air 
discharge

A

B

B

C

C

D

C

C

A

D

A

C

D

D

3-way air 
discharge

3-way air 
discharge

2-way air 
discharge

2-way air 
discharge

Optional parts required 
(Back-to-back blocking pad kit)

01_EN_3P249378-5G.fm  Page 3  Friday, January 20, 2012  2:01 PM

Summary of Contents for FUY71FJV1

Page 1: ...RE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGV...

Page 2: ...eenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas seg n lo enmendado secondo le prescrizioni per Direttive come da modifica de acordo com o previsto...

Page 3: ...71BV1 FHYP100BV1 FHYP125BV1 FH35BZV1 FH45BZV1 FH60BZV1 III FHQ35BUV1B FHQ50BUV1B FHQ60BUV1B FHQ71BUV1B FHQ100BUV1B FHQ125BUV1B FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B FUQ71...

Page 4: ...t and never connect additional wiring to the existing circuit An insufficient power supply capacity or improper electrical work may lead to electric shocks or fire Be sure to earth the air conditioner...

Page 5: ...here the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels 2 2 ACCESSORIES Check the following acc...

Page 6: ...rection therefore select flow direction from the below patterns Air flow patterns Refer to Fig 1 IIlustrations seen from ceiling A B C and D indicate drain pans Refrigerant pipe direction To the rear...

Page 7: ...Fig 4 and 5 Slide the locking knobs 2 on the air intake grille inward direction of arrows and lift upwards Fig 4 Fig 5 Open the air intake grille to a 45 angle and detach from the unit Detach the corn...

Page 8: ...hole in anchor for existing ceilings and a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the...

Page 9: ...ged by sliding the shutter Refer to Fig 14 CAUTION Be careful not to touch the heat exchanger fins 2 way air discharge Refer to Fig 15 NOTE Illustrations seen from ceiling Fig 15 Retainers for blockin...

Page 10: ...18 Lock the unit to the hangers on side A Hook the unit onto the other 2 hangers and lock with bottom washers and nuts 5 3 Check whether the unit is horizontally level from sides C and D both Refer t...

Page 11: ...ly ester oil or ether oil to the inside of the flare section and spin 3 4 times before screwing in Refer to Fig 22 CAUTION Do not let oil get on the screw holders on the dressing board Oil can weaken...

Page 12: ...a flared or a flanged connection Nitrogen should be set to 0 02MPa with a pressure reducing valve if brazing while inserting nitrogen into the piping Refer to Fig 25 Fig 25 7 DRAIN PIPING WORK 7 1 Ri...

Page 13: ...ing after the test run is complete Remove the control box lid and change the emergency switch above the PC board assembly of the indoor unit from NORM to EMERG Connect the single phase power supply an...

Page 14: ...wires After all the wiring connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside...

Page 15: ...g ceiling height Select the SECOND CODE NO that corresponds to the ceiling height Refer to Table 5 and 6 SECOND CODE NO is factory set to 01 for a ceiling height of less than 2 7m Table 5 Table 6 10 2...

Page 16: ...the end of the setting procedure You do not need to rewire the remote controller from the master unit if the optional remote controller for slave unit is used However remove the wires attached to the...

Page 17: ...rystal display In such a case diagnose the fault contents by referning to the table on the Error code list it case of group control the unit No is displayed so that the indoor unit no with the trouble...

Page 18: ...4 Low pressure switch faulty outdoor unit H7 Outdoor fan motor position signal malfunction out door unit H9 Outdoor air thermistor faulty outdoor unit NOTE 1 J1 Pressure sensor system error batch outd...

Page 19: ...elivering the product to the customer after the test run is completed check that the control box lid the air filter and the suction grille are mounted In addition explain to the customer regarding the...

Page 20: ...NG CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED 5 REMOTE CONTROLLER MO...

Page 21: ...RMINAL CONNECTOR 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTRO...

Page 22: ...TEM SEE THE INDOOR UNIT WIRING ONLY 4 FOR THE DETAIL SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT 5 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTAL...

Page 23: ...1201 3P249378 5G EM11A075 HT 00_CV_3P249378 5G fm Page 2 Thursday December 8 2011 4 16 PM...

Reviews: