background image

11

English

8.

ELECTRIC WIRING WORK

• All field supplied parts and materials and electric works 

must conform to local codes.

• Use copper wire only.
• For electric wiring work, refer also to “WIRING DIAGRAM” 

attached to the unit body.

• For remote controller wiring details, refer to the installation 

manual attached to the remote controller.

• All wiring must be performed by an authorized electrician.
• A circuit breaker capable of shutting down power supply to 

the entire system must be installed.

• Refer to the installation manual attached to the outdoor unit 

for the size of power supply electric wire connected to the 
outdoor unit, the capacity of the circuit breaker and switch, 
and wiring instructions.

• Be sure to ground the air conditioner
• Do not connect the ground wire to gas pipes, plumbing 

pipes, lightning rods, or telephone ground wires.

• Gas pipes: might cause explosions or fire if gas leaks.
• Plumbing: no grounding effect if hard vinyl piping is used. 
• Telephone ground wires or lightning rods: might cause 

abnormally high electric potential in the ground during 
lighting storms.

• Specifications for field wire

The remote control cord should be procured locally. Refer to 
the Table 4 when preparing one.

Table 4

NOTE

1. Shows only in case of protected pipes. Use H07RN-F in 

case of no protection.

2. Insulated thickness : 1mm or more

<Methods of wiring units and connecting remote control-
ler cords> (Refer to Fig. 32)

• Wiring the units connections

Remove the switch box cover, and align the phases with 
those of the power terminal block inside to connect. 
Securely fix the wires with the included clamp material A, 
then fix them with the clamp material C likewise.

• Remote controller cords connections

(not necessary for slave unit of simultaneous operation sys-
tem)
Connect to the remote controller terminal block. (no polarity)
Securely fix the remote controller cord with the included 
clamp material B, then fix it with the clamp material D like-
wise.

CAUTION

• When clamping wiring, use the included clamping material 

to prevent outside pressure being exerted on the wiring con-
nections and clamp firmly. When doing the wiring, make 
sure the wiring is neat and does not cause the control box 
lid to stick up, then close the cover firmly.

• When attaching the control box lid, make sure you do not 

pinch any wires.

• After all the wiring connections are done, fill in any gaps in 

the through holes with putty or insulation (procured locally) 
to prevent small animals and insects from entering the unit 
from outside. (If any do get in, they could cause short cir-
cuits in the electric box.)

• Outside the machine, separate the weak wiring (remote con-

trol cord) and strong wiring (interunit, ground, and other 
power wiring) at least 50 mm so that they do not pass 
through the same place together. Proximity may cause elec-
trical interference, malfunctions, and breakage.

CAUTION

• Do not connect wires of different gauge to the same power 

supply terminal.
(Looseness in the connection may cause overheating.)

• Observe the notes when wiring to the power supply terminal 

board.
(Use a round crimp-style terminal with insulation sleeve for 
connection to the power supply terminal board. In case it 
cannot be used due to unavoidable reasons, connect wires 
of the same gauge to the both side as shown in Fig. 33.)

Follow the instructions below if the wiring gets very hot 
due to slack in the power wiring.

• In wiring, make certain that prescribed wires are used, carry 

out complete connections, and fix the wires so that outside 
forces are not applied to the terminals.

• Use the correct screwdriver for tightening the terminal 

screws. If the blade of screwdriver is too small, the head of 
the screw might be damaged, and the screw will not be 
properly tightened.

• If the terminal screw are tightened too hard, screws might 

be damaged.

• Refer to the table below for the tightening torque of the ter-

minal screws.

Wire

Size (mm

2

)

Length

Wiring the units

H05VV - U4G

(NOTE 1)

2.5

Remote
controller cord

Vinyl cord with 

sheath or cable

(2 wire) (NOTE 2)

0.75 - 1.25

Max. 

500m

P1

P2

How to connect wiring

Blue

Blue

Remote controller cord

Clamp A

Ground terminal

Clamp B

Clamp C and D

Clamp D

Remote controller 
transmission wire
Power supply wire

Clamp C

Fig. 32

Tab

Wiring the units

How to connect power supply 
terminal board (4P)

Terminal board for remote 
controller (2P)

Power supply 
terminal
board (4P)

1 2 3

Tightening torque (N

·

m)

Terminal block for remote 
controller

0.79 to 0.97

Terminal block for wiring the 
units

1.18 to 1.44

Earth terminal

1.44 to 1.94

Electric wire

Round 
crimp-style 
terminal

Attach insulation sleeve

Connect wires of 
the same gauge to 
both side.(GOOD)

Do not connect wires 
of the same gauge to 
one side.(WRONG)

Fig. 33

Do not connect 
wires of different 
gauges.(WRONG)

01_EN_3P249378-5G.fm  Page 11  Friday, January 20, 2012  2:01 PM

Summary of Contents for FUY71FJV1

Page 1: ...RE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGV...

Page 2: ...eenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas seg n lo enmendado secondo le prescrizioni per Direttive come da modifica de acordo com o previsto...

Page 3: ...71BV1 FHYP100BV1 FHYP125BV1 FH35BZV1 FH45BZV1 FH60BZV1 III FHQ35BUV1B FHQ50BUV1B FHQ60BUV1B FHQ71BUV1B FHQ100BUV1B FHQ125BUV1B FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B FUQ71...

Page 4: ...t and never connect additional wiring to the existing circuit An insufficient power supply capacity or improper electrical work may lead to electric shocks or fire Be sure to earth the air conditioner...

Page 5: ...here the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels 2 2 ACCESSORIES Check the following acc...

Page 6: ...rection therefore select flow direction from the below patterns Air flow patterns Refer to Fig 1 IIlustrations seen from ceiling A B C and D indicate drain pans Refrigerant pipe direction To the rear...

Page 7: ...Fig 4 and 5 Slide the locking knobs 2 on the air intake grille inward direction of arrows and lift upwards Fig 4 Fig 5 Open the air intake grille to a 45 angle and detach from the unit Detach the corn...

Page 8: ...hole in anchor for existing ceilings and a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the...

Page 9: ...ged by sliding the shutter Refer to Fig 14 CAUTION Be careful not to touch the heat exchanger fins 2 way air discharge Refer to Fig 15 NOTE Illustrations seen from ceiling Fig 15 Retainers for blockin...

Page 10: ...18 Lock the unit to the hangers on side A Hook the unit onto the other 2 hangers and lock with bottom washers and nuts 5 3 Check whether the unit is horizontally level from sides C and D both Refer t...

Page 11: ...ly ester oil or ether oil to the inside of the flare section and spin 3 4 times before screwing in Refer to Fig 22 CAUTION Do not let oil get on the screw holders on the dressing board Oil can weaken...

Page 12: ...a flared or a flanged connection Nitrogen should be set to 0 02MPa with a pressure reducing valve if brazing while inserting nitrogen into the piping Refer to Fig 25 Fig 25 7 DRAIN PIPING WORK 7 1 Ri...

Page 13: ...ing after the test run is complete Remove the control box lid and change the emergency switch above the PC board assembly of the indoor unit from NORM to EMERG Connect the single phase power supply an...

Page 14: ...wires After all the wiring connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside...

Page 15: ...g ceiling height Select the SECOND CODE NO that corresponds to the ceiling height Refer to Table 5 and 6 SECOND CODE NO is factory set to 01 for a ceiling height of less than 2 7m Table 5 Table 6 10 2...

Page 16: ...the end of the setting procedure You do not need to rewire the remote controller from the master unit if the optional remote controller for slave unit is used However remove the wires attached to the...

Page 17: ...rystal display In such a case diagnose the fault contents by referning to the table on the Error code list it case of group control the unit No is displayed so that the indoor unit no with the trouble...

Page 18: ...4 Low pressure switch faulty outdoor unit H7 Outdoor fan motor position signal malfunction out door unit H9 Outdoor air thermistor faulty outdoor unit NOTE 1 J1 Pressure sensor system error batch outd...

Page 19: ...elivering the product to the customer after the test run is completed check that the control box lid the air filter and the suction grille are mounted In addition explain to the customer regarding the...

Page 20: ...NG CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED 5 REMOTE CONTROLLER MO...

Page 21: ...RMINAL CONNECTOR 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTRO...

Page 22: ...TEM SEE THE INDOOR UNIT WIRING ONLY 4 FOR THE DETAIL SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT 5 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTAL...

Page 23: ...1201 3P249378 5G EM11A075 HT 00_CV_3P249378 5G fm Page 2 Thursday December 8 2011 4 16 PM...

Reviews: