background image

English

8

6.

REFRIGERANT PIPING WORK

For refrigerant piping of outdoor units, see the installa-

tion manual attached to the outdoor unit.

〉 

Execute heat insulation work completely on both sides of 

the gas piping and the liquid piping. 
Otherwise, a water leakage can result sometimes.

〉 

(

When using a heat pump, the temperature of the gas piping 

can reach up to approximately 120°C, so use insulation which 
is sufficiently resistant.)

Also, in cases where the temperature and humidity of the 

refrigerant piping sections might exceed 30°C or RH80 %, 
reinforce the refrigerant insulation. (20 mm or thicker) 
Condensation may form on the surface of the insulating 
material.

Before refrigerant piping work, check which type of refrig-

erant is used. Proper operation is not possible if the types 
of refrigerant are not the same.

CAUTION

• Use a pipe cutter and flare suitable for the type of refrig-

erant.

• Apply ester oil or ether oil around the flare section 

before connecting.

• To prevent dust, moisuture or other foreign matter from 

infiltrating the tube, either pinch the end or cover it with 
tape.

• Do not allow anything other than the designated refrig-

erant to get mixed into the refrigerant circuit, such as 
air, etc. If any refrigerant gas leaks while working on the 
unit, ventilate the room thoroughly right away.

6-1 Refrigerant pipes can be run in 3 directions 

(Refer to Fig. 20)

• Use copper alloy seamless pipes (ISO 1337).
• The outdoor unit is charged with refrigerant.
• Be sure to use both a spanner and torque wrench 

together, when connecting or disconnecting pipes to/
from the unit. 

(Refer to Fig. 21)

• Refer to the Table 2 for flare dimensions and tightening 

torque.

NOTE

• Use the flare nut included with the unit main body.

• When connecting the flare nut, apply ester oil or ether 

oil to the inside of the flare section, and spin 3-4 times 
before screwing in. 

(Refer to Fig. 22)

CAUTION

Do not let oil get on the screw holders on the dressing board. 
Oil can weaken the screw holders.

Table 2

• Refer to “Table 2” to determine the proper tightening torque.

CAUTION

• Over-tightening the flare nut may break it and/or cause the 

refrigerant to leak.

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to install 
the unit without a torque wrench, you may follow the installation 
method mentioned below.

After the work is finished, make sure to check that there is 
no gas leak.

When you keep on tightening the flare nut with a spanner, there 
is a point where the tightening torque suddenly increases. 
From that position, further tighten the flare nut the angle shown 
below:

Table 3

• Make absolutely sure to execute heat insulation works on 

the pipe-connecting section after checking gas leakage by 
thoroughly studying the following figure and using the 
attached heat insulating materials for couplings (6) and (7).  
(Fasten both ends with the clamps (4).) 

(Refer to Fig. 23)

Upward running pipes

Rear running pipes

Right running pipes

Fig. 20

Piping union

Torque wrench

Spanner

Flare nut

Fig. 21

Pipe size

Further tightening angle

Recommended arm 
length of tool

φ

9.5 (3/8”)

60 to 90 degrees

Approx. 200mm

φ

15.9 (5/8”)

30 to 60 degrees

Approx. 300mm

φ

19.1 (3/4”)

25 to 35 degrees

Approx. 450mm

Fig. 22

Coat here with ester or ether oil.

Type of refrigerant

Applicable model

Flare dimensions A (mm)

R22, R407C

FUY-FJV1

FUYP-BV1

R410A

FUQ

Pipe size Tightening torque

R0.4-0.8

A

90˚±2˚ 

45˚±2˚

32.7-39.9 N • m

61.8-75.4 N • m

97.2-118.8 N • m

Flare

12.6 – 13.0

19.0 – 19.4

23.3 – 23.7

12.8 – 13.2

19.3 – 19.7

φ

9.5(3/8”)

φ

15.9(5/8”)

φ

19.1(3/4”)

Insulation for gas 
pipe (6) (accessory)

Insulation for liquid 
pipe (7) (accessory)

Clamp (4)
(×4) (accessory)

Fig. 23

Attach to tha root

01_EN_3P249378-5G.fm  Page 8  Friday, January 20, 2012  2:01 PM

Summary of Contents for FUY71FJV1

Page 1: ...RE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGV...

Page 2: ...eenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas seg n lo enmendado secondo le prescrizioni per Direttive come da modifica de acordo com o previsto...

Page 3: ...71BV1 FHYP100BV1 FHYP125BV1 FH35BZV1 FH45BZV1 FH60BZV1 III FHQ35BUV1B FHQ50BUV1B FHQ60BUV1B FHQ71BUV1B FHQ100BUV1B FHQ125BUV1B FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B FUQ71...

Page 4: ...t and never connect additional wiring to the existing circuit An insufficient power supply capacity or improper electrical work may lead to electric shocks or fire Be sure to earth the air conditioner...

Page 5: ...here the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels 2 2 ACCESSORIES Check the following acc...

Page 6: ...rection therefore select flow direction from the below patterns Air flow patterns Refer to Fig 1 IIlustrations seen from ceiling A B C and D indicate drain pans Refrigerant pipe direction To the rear...

Page 7: ...Fig 4 and 5 Slide the locking knobs 2 on the air intake grille inward direction of arrows and lift upwards Fig 4 Fig 5 Open the air intake grille to a 45 angle and detach from the unit Detach the corn...

Page 8: ...hole in anchor for existing ceilings and a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the...

Page 9: ...ged by sliding the shutter Refer to Fig 14 CAUTION Be careful not to touch the heat exchanger fins 2 way air discharge Refer to Fig 15 NOTE Illustrations seen from ceiling Fig 15 Retainers for blockin...

Page 10: ...18 Lock the unit to the hangers on side A Hook the unit onto the other 2 hangers and lock with bottom washers and nuts 5 3 Check whether the unit is horizontally level from sides C and D both Refer t...

Page 11: ...ly ester oil or ether oil to the inside of the flare section and spin 3 4 times before screwing in Refer to Fig 22 CAUTION Do not let oil get on the screw holders on the dressing board Oil can weaken...

Page 12: ...a flared or a flanged connection Nitrogen should be set to 0 02MPa with a pressure reducing valve if brazing while inserting nitrogen into the piping Refer to Fig 25 Fig 25 7 DRAIN PIPING WORK 7 1 Ri...

Page 13: ...ing after the test run is complete Remove the control box lid and change the emergency switch above the PC board assembly of the indoor unit from NORM to EMERG Connect the single phase power supply an...

Page 14: ...wires After all the wiring connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside...

Page 15: ...g ceiling height Select the SECOND CODE NO that corresponds to the ceiling height Refer to Table 5 and 6 SECOND CODE NO is factory set to 01 for a ceiling height of less than 2 7m Table 5 Table 6 10 2...

Page 16: ...the end of the setting procedure You do not need to rewire the remote controller from the master unit if the optional remote controller for slave unit is used However remove the wires attached to the...

Page 17: ...rystal display In such a case diagnose the fault contents by referning to the table on the Error code list it case of group control the unit No is displayed so that the indoor unit no with the trouble...

Page 18: ...4 Low pressure switch faulty outdoor unit H7 Outdoor fan motor position signal malfunction out door unit H9 Outdoor air thermistor faulty outdoor unit NOTE 1 J1 Pressure sensor system error batch outd...

Page 19: ...elivering the product to the customer after the test run is completed check that the control box lid the air filter and the suction grille are mounted In addition explain to the customer regarding the...

Page 20: ...NG CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED 5 REMOTE CONTROLLER MO...

Page 21: ...RMINAL CONNECTOR 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTRO...

Page 22: ...TEM SEE THE INDOOR UNIT WIRING ONLY 4 FOR THE DETAIL SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT 5 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTAL...

Page 23: ...1201 3P249378 5G EM11A075 HT 00_CV_3P249378 5G fm Page 2 Thursday December 8 2011 4 16 PM...

Reviews: