background image

English

7

Note:

1) Wrap the refrigerant pipes and drain hose together with insulation tape as 

right figure, in case of setting the drain hose through the back of the 
indoor unit.

2) If it difficult to fix the claws of the bottom frame on the catches of the 

mounting plate.
Secure indoor unit to the mounting plate with screws (M4 × 12L).

3-3. Wall embedded piping.

Follow the instructions given under  

.

1) Insert the drain hose to this depth so it wont be pulled out of the drain 

pipe.

4.

Wiring.

 WARNING

1) Do not use tapped wires, stand wires, extensioncords, or starbust connections, as they may cause overtheating, electrical 

shock,or fire.

2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

3) Be sure to install an earth leak detector. (Failure to install an earth leakage breaker may result in electric shocks.)
4) When wiring indoor and outdoor units, always connect terminals together having the same numbers.

Should any terminal be connected to another terminal that has a different number, the air conditioner may stop running, or the 
fuse on the indoor or outdoor unit may blow out. 
(See the electric wiring diagram included with the product for details on the fuse specifications.)

• Do not turn ON the safety breaker until all work is completed.

1) Strip wire ends (15mm).
2) Match wire colours with terminal numbers on indoor and outdoor units’ terminal blocks and firmly screw wires to the corre-

sponding terminals.

3) Connect the earth wires to the corresponding terminals.
4) Pull wires to make sure that they are securely latched up, then retain wires with wire retainer.
5) Shape the wires so that the service lid fits securely, then close service lid.

Refrigerant
pipes

Drain hose

Bottom frame

Mounting
plate

A

G  M4 

×

 12L (2 point)

Inner wall

Vinyl chloride 
drain pipe 
(VP-30)

Drain hose

50mm 
or more

Insert drain hose 
to this depth so 
it won’t be pulled 
out of drain pipe.

Outer wall

Left-side, left-back, or left-bottom piping

1

2 3

4 5

Terminal block

Electrical component box

Wire retainer

Use the specified wire type.

Firmly secure wire retainer 
so that wires sustain no 
external stress.

Firmly fix the wires with 
the terminal screws.

Shape wires so that the 
service lid will fit securely.

3

4

5

2
1

1 2 3 4 5 L N E

Earth

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor unit

Power
supply
50Hz 220-240V

Firmly fix the wires with 
the terminal screws.

H05RN

Thermistor cable (Included with the indoor unit)

Safety 
breaker 
10A

Earth leakage 
circuit breaker

The earth leakage circuit 
breaker is required depending
on site environment. 

Interconnecting wires

Specification for field wire

Wire

Size (mm

2

)

Number of core

Interconnecting wires

H05RN

1.0

4

Power supply wire

1.5

3

01_EN_3P211822-1C.fm  Page 7  Tuesday, November 27, 2007  6:30 PM

Summary of Contents for FTYN25GXV1B

Page 1: ...Installationsanleitung Split Baureihe R410A Montaj k lavuzlar R410A Split serisi Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie Split R410A...

Page 2: ...7 08 Nota 09 p 10 Bem rk 11 Information 12 Merk 13 Huom 14 Pozn mka 15 Napomena 16 Megjegyz s 17 Uwaga 18 Nota 19 Opomba 20 M rkus 21 22 Pastaba 23 Piez mes 24 Pozn mka 25 Not 3SB64204 1A FTYN25GXV1B...

Page 3: ...ape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fir...

Page 4: ...Installation manual 1 AAA dry cell batteries 2 Drain plug 1 The indoor unit should be sited in a place where the restrictions on installation specified in the indoor unit installation drawings are me...

Page 5: ...more from walls on both sides Service lid Opening service lid Service lid is opening closing type Opening method 1 Remove the service lid screws 2 Pull out the service lid diagonally down in the direc...

Page 6: ...alls facing three sides Side view More than 50 More than 100 Top view More than 50 More than 50 More than 100 More than 150 Top view More than 50 More than 150 More than 300 Construct a large canopy C...

Page 7: ...o prevent possible heat electrical shock or fire Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage 1 Bore a feed through hole of 65mm in the wall so it has a d...

Page 8: ...drain port in place of a drain plug 3 Shape the refrigerant pipe along the pipe path marking on the mounting plate 4 Pass drain hose and refrigerant pipes through the wall hole then set the indoor uni...

Page 9: ...s Do not turn ON the safety breaker until all work is completed 1 Strip wire ends 15mm 2 Match wire colours with terminal numbers on indoor and outdoor units terminal blocks and firmly screw wires to...

Page 10: ...vinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use any commercially available drain socket nominal diameter 13mm as a joi...

Page 11: ...ipes and fittings observe the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C m...

Page 12: ...es from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no...

Page 13: ...nutes close the gas stop valve and stop forced cool ing operation 6 Wiring For interconnecting wire connections see Indoor Unit 4 Wiring Gas stop valve Valve cap Hexagonal wrench Close Liquid stop val...

Page 14: ...the wire and make sure that it does not disconnect Then fix the wire in place with a wire stop 7 Drain work 1 Use drain plug for drainage 2 If the drain port is covered by a mounting base or floor su...

Page 15: ...tandby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power...

Page 16: ...0712 HT 3P211822 1C M07B070B Two dimensional bar code is a code for manufacturing...

Reviews: