English
3
Indoor/Outdoor Unit
Installation Drawings
Foot bolt-hole
centres
311
574
(Foot bolt-hole centres)
(From unit’
s side)
105.5
Where there is a danger of the unit
falling, use foot bolts, or wires.
Allow space for piping
and electrical servicing.
unit: mm
How to remove the stop
valve cover.
Remove the screw on the
stop valve cover.
Slide the lid downward
to remove it.
How to attach the stop
valve cover.
Insert the upper part of
the stop valve cover into the
outdoor unit to install.
Tighten the screws.
Stop valve cover
In sites with poor drainage, use block
bases for outdoor unit. Adjust foot height
until the unit is leveled. Otherwise, water
leakage or pooling of water may occur.
250mm from wall
Air-Purifying Filter
with bacteriostatic,
virustatic function
Filter frame
Air filter
Tab
M4 × 12L
Wrap the insulation pipe with
the finishing tape from bottom
to top.
Cut thermal insulation
pipe to an appropriate
length and wrap it with
tape, making sure that no
gap is left in the insulation
pipe’s cut line.
Caulk
pipe hole
gap
with putty.
30mm or more from ceiling
Front panel
50mm or more from walls
(on both sides)
Service lid
Opening service lid
Service lid is opening/closing type.
Opening method
1) Remove the service lid screws.
2) Pull out the service lid diagonally
down in the direction of the arrow.
3) Pull down.
Air filter
A
Mounting
plate
Clip
Mark (rear side)
Bottom frame
How to attach the indoor unit.
Hook the claws of the bottom frame
to the mounting plate.
If the claws are difficult to hook,
remove the front grille.
How to remove the indoor unit.
Push up the marked area (at the
lower part of the front grille) to
release the claws. If it is difficult to
release, remove the front grille.
Front
grille
Air-Purifying Filter with bacteriostatic,
virustatic function (2)
25
35
Gas pipe
Liquid pipe
O.D. 6.4mm
O.D. 9.5mm O.D. 12.7mm
Max. allowable length
Max. allowable length without
additional charge
*
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced perfomance.
15m
10m
Min. allowable length
Model
3m
Additional charge of refrigerant
Max. allowable height
20g/m
10m
C
D
Wireless
remote
controller
E
Remote
controller
holder
Screws
(Field supply: M3 × 20L)
Before screwing
the remote
controller holder
to the wall, make
sure that control
signals are
properly received
by indoor unit.
A
Mounting plate
Mounting plate
fixing screw
(Field supply: M4 × 25L)
01_EN_3P211822-1C.fm Page 3 Tuesday, November 27, 2007 6:30 PM