Indoor Unit 

1.

Installing the mounting plate.

• The mounting plate should be installed on a wall which can support the weight of the indoor unit.

1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring 

points on the wall.

2) Secure the mounting plate to the wall with screws.

Recommended mounting plate retention spots and Dimensions

2.

Boring a wall hole and installing wall embedded pipe.

• For walls containing metal frame or metal board, be sure to use a wall embed-

ded pipe and wall cover in the feed-through hole to prevent possible heat, 
electrical shock, or fire.

• Be sure to caulk the gaps around the pipes with caulking material to prevent 

water leakage.
1) Bore a feed-through hole of 65mm in the wall so it has a down slope toward 

the outside.

2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole 

gap with putty.

800

184

54.5

153.8

181.7

55.5

263

51.9

166

42.2

45.9

288

42.2

45.9

Recommended mounting 
plate retention spots. 
(5 spots in all)

Liquid pipe end

Gas pipe end

Use tape measure 
as shown. 
Position the end 
of a tape measure 
at    .

Drain hose position

Through the wall 
hole 

φ

65mm

Inside

Outside

Caulking

Wall embedded pipe 
(Field supply)

Wall hole cover
(Field supply)

Wall embedded pipe 
(Field supply)

φ

65

01_EN_3P211822-1C.fm  Page 5  Tuesday, November 27, 2007  6:30 PM

Summary of Contents for FTYN25GXV1B

Page 1: ...Installationsanleitung Split Baureihe R410A Montaj k lavuzlar R410A Split serisi Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie Split R410A...

Page 2: ...7 08 Nota 09 p 10 Bem rk 11 Information 12 Merk 13 Huom 14 Pozn mka 15 Napomena 16 Megjegyz s 17 Uwaga 18 Nota 19 Opomba 20 M rkus 21 22 Pastaba 23 Piez mes 24 Pozn mka 25 Not 3SB64204 1A FTYN25GXV1B...

Page 3: ...ape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fir...

Page 4: ...Installation manual 1 AAA dry cell batteries 2 Drain plug 1 The indoor unit should be sited in a place where the restrictions on installation specified in the indoor unit installation drawings are me...

Page 5: ...more from walls on both sides Service lid Opening service lid Service lid is opening closing type Opening method 1 Remove the service lid screws 2 Pull out the service lid diagonally down in the direc...

Page 6: ...alls facing three sides Side view More than 50 More than 100 Top view More than 50 More than 50 More than 100 More than 150 Top view More than 50 More than 150 More than 300 Construct a large canopy C...

Page 7: ...o prevent possible heat electrical shock or fire Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage 1 Bore a feed through hole of 65mm in the wall so it has a d...

Page 8: ...drain port in place of a drain plug 3 Shape the refrigerant pipe along the pipe path marking on the mounting plate 4 Pass drain hose and refrigerant pipes through the wall hole then set the indoor uni...

Page 9: ...s Do not turn ON the safety breaker until all work is completed 1 Strip wire ends 15mm 2 Match wire colours with terminal numbers on indoor and outdoor units terminal blocks and firmly screw wires to...

Page 10: ...vinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use any commercially available drain socket nominal diameter 13mm as a joi...

Page 11: ...ipes and fittings observe the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C m...

Page 12: ...es from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no...

Page 13: ...nutes close the gas stop valve and stop forced cool ing operation 6 Wiring For interconnecting wire connections see Indoor Unit 4 Wiring Gas stop valve Valve cap Hexagonal wrench Close Liquid stop val...

Page 14: ...the wire and make sure that it does not disconnect Then fix the wire in place with a wire stop 7 Drain work 1 Use drain plug for drainage 2 If the drain port is covered by a mounting base or floor su...

Page 15: ...tandby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power...

Page 16: ...0712 HT 3P211822 1C M07B070B Two dimensional bar code is a code for manufacturing...

Reviews: