![background image](http://html1.mh-extra.com/html/daikin/ftxta30aw/ftxta30aw_service-manual_4214030029.webp)
ESIE17-19C
|
Part 2. Troubleshooting
2.2. Error based troubleshooting
19/08/19
|
Version 1.1
Page 29
Optimized Heating 4
2.2.2.7. “E9-00” – Electronic expansion valve abnormality (units with no pressure sensor)
More info:
2.2.2.8. “EA-00” – 4-way valve abnormality
Trigger
Effect
Reset
1. No continuity of expansion valve.
2. Minimum expansion valve opening
and suction superheat < A K and
discharge superheat < B K.
Unit will stop operating.
Manual reset via user interface.
Power reset via outdoor unit.
Possible cause
Check
Corrective action
Wet operation.
Check for wet operation. (Wet operation
can be detected by checking the suction
superheat. If the suction superheat is 0°C
then liquid refrigerant is returned to the
compressor.)
In case wet operation was detected, con-
firm the cause:
• Refrigerant
overcharge.
• Faulty expansion valve.
Faulty outdoor unit main PCB.
Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when HAP
LED is not blinking in regular intervals.
Faulty thermistor.
Check thermistor.
Replace thermistor when required.
Faulty or disturbance of the power supply
(imbalance >10%). Power drop. Short cir-
cuit.
Check if the power supply is conform with
regulations. No fluctuations in frequency.
Adjust power supply when required.
Power reset via outdoor unit.
Faulty expansion valve.
Check the expansion valve.
Replace the expansion valve body or
motor when required.
Faulty capacity adapter on outdoor PCB.
Check if the correct adapter is installed.
Check if the correct spare part is installed.
Adjust capacity adapter when required.
External factory (e.g. electrical noise)
(cause when error is reset after power
reset, and error happens again after a
while).
Check for source which could cause elec-
trical interference.
Avoid electrical interference.
Check procedures
Replacing procedures
"Replacing main PCB" on page 95
"Refrigerant thermistors" on page 60
"Electronic expansion valve" on page 53
"Replacing expansion valve body" on page 89
"Product specific information" on page 118
Trigger
Effect
Reset
The room thermistor / indoor heat
exchanger are not functioning within oper-
ation range.
Unit will not stop operating.
Automatic reset when unit runs without
error for 60 minutes.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty 4-way valve coil.
Check 4-way valve coil.
Replace 4-way valve coil when required.
Faulty 4-way valve body, blocked.
Check 4-way valve body.
Replace 4-way valve body when required.