Control Specification
28
Function and Control
3.2
Frequency Control
Outline
Frequency will be determined according to the difference between room and set temperature.
The function is explained as follows.
1. How to determine frequency.
2. Frequency command from an indoor unit. The difference between a room temperature and the
temperature set by the remote controller.
3. Frequency command from an indoor unit.
4. Frequency initial setting.
5. PI control.
Detail
How to Determine Frequency
The compressor’s frequency is determined by taking the following steps:
For Heat Pump Model
1. Determine command frequency
Command frequency will be determined in the following order of priority.
1.1 Limiting frequency by dropping function
Input current, discharge pipes, low Hz high pressure limit, peak cutting, freeze prevention, dew
prevention, fin thermistor temperature.
1.2 Limiting defrost control time
1.3 Forced cooling
1.4 Indoor frequency command
2. Determine upper limit frequency
Set a minimum value as an upper limit frequency among the frequency upper limits of the
following functions:
Compressor protection, input current, discharge pipes, Low Hz high pressure, peak cutting,
freeze prevention, defrost.
3. Determine lower limit frequency
Set a maximum value as an lower limit frequency among the frequency lower limits of the
following functions:
Four-way valve operating compensation, draft prevention, pressure difference stabilization.
4. Determine prohibited frequency
There is a certain prohibited frequency such as a power supply frequency.
Command frequency
Limit frequency
Skip control
Upper limit function
Compressor protection function
Lower limit function
Four-way valve operating compensation, etc. (*)
Initial frequency
PI control
Defrost control (*)
Dropping function
Input current control, etc.
Upper limit frequency
Lower limit frequency
FMIN
Target frequency
Command frequency X repeats when frequency becomes lower
Frequency changes by PI control < repeats when frequency becomes lower
*; only for heat pump model
(R2831)
Summary of Contents for FTXS30HVJU
Page 1: ...SiUS04 924 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series ...
Page 8: ...SiUS04 924 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 10: ...SiUS04 924 Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Page 50: ...Control Specification SiUS04 924 Function and Control 43 ...
Page 53: ...Instruction SiUS04 924 46 Operation Manual 2 Instruction 2 1 Remote Controller ...
Page 54: ...SiUS04 924 Instruction Operation Manual 47 operation ...
Page 55: ...Instruction SiUS04 924 48 Operation Manual 2 2 AUTO DRY COOL HEAT FAN Operation ...
Page 56: ...SiUS04 924 Instruction Operation Manual 49 ...
Page 58: ...SiUS04 924 Instruction Operation Manual 51 fins fins fins fins angles Inside ...
Page 60: ...SiUS04 924 Instruction Operation Manual 53 2 5 INTELLIGENT EYE Operation fins above ...
Page 61: ...Instruction SiUS04 924 54 Operation Manual ...
Page 62: ...SiUS04 924 Instruction Operation Manual 55 2 6 POWERFUL Operation ...
Page 63: ...Instruction SiUS04 924 56 Operation Manual 2 7 OUTDOOR UNIT QUIET Operation ...
Page 64: ...SiUS04 924 Instruction Operation Manual 57 2 8 ECONO Operation ...
Page 65: ...Instruction SiUS04 924 58 Operation Manual 2 9 TIMER Operation ...
Page 66: ...SiUS04 924 Instruction Operation Manual 59 ...
Page 69: ...Instruction SiUS04 924 62 Operation Manual ...
Page 70: ...SiUS04 924 Instruction Operation Manual 63 ...
Page 71: ...Instruction SiUS04 924 64 Operation Manual ...
Page 72: ...SiUS04 924 Instruction Operation Manual 65 3P228444 2B ...
Page 193: ...SiUS04 924 187 Appendix Part 9 Appendix 1 Piping Diagrams 188 2 Wiring Diagrams 189 ...