Troubleshooting
Service Diagnosis
97
4.20 Electrical Box Temperature Rise
Remote
Controller
Display
L3
Method of
Malfunction
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Malfunction
Decision
Conditions
With the compressor off, the radiation fin temperature is above 212°F(100°C). (Reset is made when
the temperature drops below 158°F(70°C).)
Supposed
Causes
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
Foreign matter stuck in the outdoor unit fan
Troubleshooting
Check No.07
Refer to P.109
Check No.09
Refer to P.110
(R9294)
Caution
Be sure to turn off the power switch before connecting or disconnecting
the connector, or parts damage may occur.
YES
NO
Slightly dirty
Malfunctioning
Too dirty
Functioning
NO
YES
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 185°F(85°C) and stops
itself when it drops below
Turn off the power and turn it on
again.
Check the radiation fin
temperature.
Check No. 07
Check the installation condition.
Radiation fin
dirty?
Above its stop
level?
Check No. 09
Check the outdoor unit fan or
related.
Error again or
outdoor unit fan activated?
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors and
fan motor leads.
Clean up the radiation fin.
Summary of Contents for FTXS30HVJU
Page 1: ...SiUS04 924 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series ...
Page 8: ...SiUS04 924 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 10: ...SiUS04 924 Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Page 50: ...Control Specification SiUS04 924 Function and Control 43 ...
Page 53: ...Instruction SiUS04 924 46 Operation Manual 2 Instruction 2 1 Remote Controller ...
Page 54: ...SiUS04 924 Instruction Operation Manual 47 operation ...
Page 55: ...Instruction SiUS04 924 48 Operation Manual 2 2 AUTO DRY COOL HEAT FAN Operation ...
Page 56: ...SiUS04 924 Instruction Operation Manual 49 ...
Page 58: ...SiUS04 924 Instruction Operation Manual 51 fins fins fins fins angles Inside ...
Page 60: ...SiUS04 924 Instruction Operation Manual 53 2 5 INTELLIGENT EYE Operation fins above ...
Page 61: ...Instruction SiUS04 924 54 Operation Manual ...
Page 62: ...SiUS04 924 Instruction Operation Manual 55 2 6 POWERFUL Operation ...
Page 63: ...Instruction SiUS04 924 56 Operation Manual 2 7 OUTDOOR UNIT QUIET Operation ...
Page 64: ...SiUS04 924 Instruction Operation Manual 57 2 8 ECONO Operation ...
Page 65: ...Instruction SiUS04 924 58 Operation Manual 2 9 TIMER Operation ...
Page 66: ...SiUS04 924 Instruction Operation Manual 59 ...
Page 69: ...Instruction SiUS04 924 62 Operation Manual ...
Page 70: ...SiUS04 924 Instruction Operation Manual 63 ...
Page 71: ...Instruction SiUS04 924 64 Operation Manual ...
Page 72: ...SiUS04 924 Instruction Operation Manual 65 3P228444 2B ...
Page 193: ...SiUS04 924 187 Appendix Part 9 Appendix 1 Piping Diagrams 188 2 Wiring Diagrams 189 ...