SiUS04-924
Function of Thermistor
26
Function and Control
2. Function of Thermistor
A Outdoor Heat
Exchanger
Thermistor
1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature.
The system sets a target discharge temperature according to the outdoor and indoor heat
exchanger temperature, and controls the electronic expansion valve opening so that the target
discharge temperature can be obtained.
2. The outdoor heat exchanger thermistor is used for detecting disconnection of the discharge
thermistor when cooling.
When the discharge pipe temperature becomes lower than the outdoor heat exchanger
temperature, the discharge pipe thermistor is judged as disconnected.
3. The outdoor heat exchanger thermistor is used for high pressure protection during cooling
operation.
B Discharge
Pipe Thermistor
1. The discharge pipe thermistor is used for controlling the temperature of the discharge pipe.
If the temperature of the discharge pipe (used in place of the inner temperature of the
compressor) rises abnormally, the operating frequency drops or the operation halts.
2. The discharge pipe thermistor is used for detecting disconnection of the discharge thermistor.
C Indoor Heat
Exchanger
Thermistor
1. The indoor heat exchanger thermistor is used for controlling target discharge temperature.
The system sets a target discharge pipe temperature according to the outdoor and indoor heat
exchanger temperature, and controls the electronic expansion valve opening so that the target
discharge temperature can be obtained.
2. The indoor heat exchanger thermistor is used for preventing freezing.
During the cooling operation, if the temperature drops abnormally, the operating frequency
owers, then the operation halts.
3. During heating: the indoor heat exchanger thermistor is used for detecting disconnection of the
discharge pipe thermistor.
When the discharge pipe temperature becomes lower than the indoor heat exchanger
temperature, the discharge pipe thermistor is judged as disconnected.
The indoor heat exchanger thermistor is also used for preventing abnormal high pressure.
Four-way valve
Compressor
(R5204)
A
C
B
Electrontic
expansion valve
Summary of Contents for FTXS30HVJU
Page 1: ...SiUS04 924 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series ...
Page 8: ...SiUS04 924 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 10: ...SiUS04 924 Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Page 50: ...Control Specification SiUS04 924 Function and Control 43 ...
Page 53: ...Instruction SiUS04 924 46 Operation Manual 2 Instruction 2 1 Remote Controller ...
Page 54: ...SiUS04 924 Instruction Operation Manual 47 operation ...
Page 55: ...Instruction SiUS04 924 48 Operation Manual 2 2 AUTO DRY COOL HEAT FAN Operation ...
Page 56: ...SiUS04 924 Instruction Operation Manual 49 ...
Page 58: ...SiUS04 924 Instruction Operation Manual 51 fins fins fins fins angles Inside ...
Page 60: ...SiUS04 924 Instruction Operation Manual 53 2 5 INTELLIGENT EYE Operation fins above ...
Page 61: ...Instruction SiUS04 924 54 Operation Manual ...
Page 62: ...SiUS04 924 Instruction Operation Manual 55 2 6 POWERFUL Operation ...
Page 63: ...Instruction SiUS04 924 56 Operation Manual 2 7 OUTDOOR UNIT QUIET Operation ...
Page 64: ...SiUS04 924 Instruction Operation Manual 57 2 8 ECONO Operation ...
Page 65: ...Instruction SiUS04 924 58 Operation Manual 2 9 TIMER Operation ...
Page 66: ...SiUS04 924 Instruction Operation Manual 59 ...
Page 69: ...Instruction SiUS04 924 62 Operation Manual ...
Page 70: ...SiUS04 924 Instruction Operation Manual 63 ...
Page 71: ...Instruction SiUS04 924 64 Operation Manual ...
Page 72: ...SiUS04 924 Instruction Operation Manual 65 3P228444 2B ...
Page 193: ...SiUS04 924 187 Appendix Part 9 Appendix 1 Piping Diagrams 188 2 Wiring Diagrams 189 ...