Troubleshooting
SiUS04-924
86
Service Diagnosis
4.13 Four-Way Valve Abnormality
Remote
Controller
Display
EA
Method of
Malfunction
Detection
The room temperature thermistor, the indoor unit heat exchanger thermistor, the outdoor
temperature thermistor and the outdoor unit heat exchanger thermistor are checked to see if they
function within their normal ranges in the operating mode.
Malfunction
Decision
Conditions
A following condition continues over 1 minute after operating 10 minutes.
Cooling / dry operation
(room temp. – indoor heat exchanger temp.) < –9°F(–5°C)
Heating
(indoor unit heat exchanger temp. – room temp.) < –9°F(–5°C)
The system will be shut down if the cooling / heating changeover abnormality occurs 5 times.
Supposed
Causes
Connector in poor contact
Thermistor defective
Outdoor unit PCB defective
Four-way valve coil or harness defective
Four-way valve defective
Foreign substance mixed in refrigerant
Insufficient gas
Summary of Contents for FTXS30HVJU
Page 1: ...SiUS04 924 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series ...
Page 8: ...SiUS04 924 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 10: ...SiUS04 924 Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Page 50: ...Control Specification SiUS04 924 Function and Control 43 ...
Page 53: ...Instruction SiUS04 924 46 Operation Manual 2 Instruction 2 1 Remote Controller ...
Page 54: ...SiUS04 924 Instruction Operation Manual 47 operation ...
Page 55: ...Instruction SiUS04 924 48 Operation Manual 2 2 AUTO DRY COOL HEAT FAN Operation ...
Page 56: ...SiUS04 924 Instruction Operation Manual 49 ...
Page 58: ...SiUS04 924 Instruction Operation Manual 51 fins fins fins fins angles Inside ...
Page 60: ...SiUS04 924 Instruction Operation Manual 53 2 5 INTELLIGENT EYE Operation fins above ...
Page 61: ...Instruction SiUS04 924 54 Operation Manual ...
Page 62: ...SiUS04 924 Instruction Operation Manual 55 2 6 POWERFUL Operation ...
Page 63: ...Instruction SiUS04 924 56 Operation Manual 2 7 OUTDOOR UNIT QUIET Operation ...
Page 64: ...SiUS04 924 Instruction Operation Manual 57 2 8 ECONO Operation ...
Page 65: ...Instruction SiUS04 924 58 Operation Manual 2 9 TIMER Operation ...
Page 66: ...SiUS04 924 Instruction Operation Manual 59 ...
Page 69: ...Instruction SiUS04 924 62 Operation Manual ...
Page 70: ...SiUS04 924 Instruction Operation Manual 63 ...
Page 71: ...Instruction SiUS04 924 64 Operation Manual ...
Page 72: ...SiUS04 924 Instruction Operation Manual 65 3P228444 2B ...
Page 193: ...SiUS04 924 187 Appendix Part 9 Appendix 1 Piping Diagrams 188 2 Wiring Diagrams 189 ...