Trial Operation and Testing

1.

Trial operation and testing.

1-1 Measure the supply voltage and make sure that it falls in the specified range.

1-2 Make sure the front panel opens and closes smoothly using remote controller. 

(Do not do this using the indoor unit operation/stop button.)

1-3 Trial operation should be carried out in either cooling or heating mode.

• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable 

temperature.

1) Trial operation may be disabled in either mode depending on the room temperature.

Use the remote control for trial operation as described below.

2) After trial operation is complete, set the temperature to a normal level (26C

°

 to 28

°

C in cooling mode, 20

°

C to 24

°

C in 

heating mode).

3) For protection, the system disables restart operation for 3 minutes after it is turned off.

1-4 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts, 

such as louver movement, are working properly.

• The air conditioner requires a small amount of power in its standby mode.  If the system is not to be used for some 

time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation 

mode when the circuit breaker is opened again.

2.

Test items.

Test items

Symptom

(diagnostic display on RC)

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for interconnecting wire connections.

Inoperative or burn damage

Indoor or outdoor unit’s air intake or exhaust has clear path of air.
Shut-off valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote controller commands.

Inoperative

1) Press ON/OFF button to turn on the system.
2) Simultaneously press centre of TEMP button and MODE button.
3) Press MODE button twice.

(“    ” will appear on the display to indicate that Trial Operation mode is selected.)

4) Trial run mode terminates in approx. 30 minutes and switches into normal mode. To quit a trial operation, press ON/OFF 

button.

Trial operation from remote controller

01_EN_3P142639-1.fm  Page 12  Monday, October 11, 2004  3:59 PM

Summary of Contents for FTXS20DVMW

Page 1: ...MW L English Deutsch Fran ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montageha...

Page 2: ...rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele 21 22 23 24 s v zhode s nasledovnou mi normou ami alebo in m i normat vnym i dokumento...

Page 3: ...hape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fi...

Page 4: ...roughout the room 7 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from...

Page 5: ...mark of the front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand When there is no work space becau...

Page 6: ...on trollers can be set for different addresses 1 In the same way as when connecting to an HA system remove the metal plate electrical wiring cover 2 Cut the address jumper JA on the printed circuit bo...

Page 7: ...pe with the finishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line Caulk pipe ho...

Page 8: ...mounting plate retention spots and Dimensions 80 100 400 135 450 283 47 5 141 5 50 5 46 5 44 5 131 5 87 44 5 110 60 130 220 50 60 110 800 65 65 Use tape measure as shown Position the end of a tape mea...

Page 9: ...plate hooks by using the markings at the top of the indoor unit as a guide 4 Open the front grille then open the service lid Refer to Installation tips 5 Pass the interconnecting wires from the outdo...

Page 10: ...the mounting plate hooks Secure indoor unit to the mounting plate with screws M4 12L 3 3 Wall embedded piping Follow the instructions given under 1 Insert the drain hose to this depth so it won t be...

Page 11: ...system 1 Remove the front grille 2 screws 2 Remove the electrical wiring box 1 screw 3 Remove the metal plate electrical wiring cover 3 tabs 4 Attach the connection cord to the S21 connector and pull...

Page 12: ...event mineral oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with...

Page 13: ...at transfer rate 0 041 to 0 052 kW mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be s...

Page 14: ...after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the origina...