Drain piping.

1) Connect the drain hose, as described below.

2) Remove the air filters and pour some water into the drain pan to check the water 

flows smoothly.

3) When drain hose requires extension, obtain an extension hose commercially avail-

able. 
Be sure to thermally insulate the indoor section of the extension hose.

4) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13 mm) directly to the drain 
hose attached to the indoor unit as with embed-
ded piping work, use any commercially available 
drain socket (nominal diameter 13 mm) as a 
joint.

Refrigerant piping work

, install as described in the installation manual supplied with the Multi outdoor unit.

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward 

so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

Warning

1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

Indoor unit 
drain hose

φ

 18

Extension drain hose

Heat insulation tube
(Field supply)

Drain hose supplied with 
the indoor unit

Commercially available drain 
socket 
(nominal diameter 13 mm)

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 13 mm)

φ

 18

With a multi indoor unit

Set exactly at the position shown below.

A

Flaring

Die

A

0 ~ 0.5 mm

Clutch-type

Flare tool for R410A

1.0 ~ 1.5 mm

Clutch-type (Rigid-type)

1.5 ~ 2.0 mm

Wing-nut type (Imperial-type)

Conventional flare tool

(Cut exactly at 

right angles.)

 Remove burrs

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

01_EN_3P142639-1.fm  Page 10  Monday, October 11, 2004  3:59 PM

Summary of Contents for FTXS20DVMW

Page 1: ...MW L English Deutsch Fran ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montageha...

Page 2: ...rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele 21 22 23 24 s v zhode s nasledovnou mi normou ami alebo in m i normat vnym i dokumento...

Page 3: ...hape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fi...

Page 4: ...roughout the room 7 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from...

Page 5: ...mark of the front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand When there is no work space becau...

Page 6: ...on trollers can be set for different addresses 1 In the same way as when connecting to an HA system remove the metal plate electrical wiring cover 2 Cut the address jumper JA on the printed circuit bo...

Page 7: ...pe with the finishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line Caulk pipe ho...

Page 8: ...mounting plate retention spots and Dimensions 80 100 400 135 450 283 47 5 141 5 50 5 46 5 44 5 131 5 87 44 5 110 60 130 220 50 60 110 800 65 65 Use tape measure as shown Position the end of a tape mea...

Page 9: ...plate hooks by using the markings at the top of the indoor unit as a guide 4 Open the front grille then open the service lid Refer to Installation tips 5 Pass the interconnecting wires from the outdo...

Page 10: ...the mounting plate hooks Secure indoor unit to the mounting plate with screws M4 12L 3 3 Wall embedded piping Follow the instructions given under 1 Insert the drain hose to this depth so it won t be...

Page 11: ...system 1 Remove the front grille 2 screws 2 Remove the electrical wiring box 1 screw 3 Remove the metal plate electrical wiring cover 3 tabs 4 Attach the connection cord to the S21 connector and pull...

Page 12: ...event mineral oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with...

Page 13: ...at transfer rate 0 041 to 0 052 kW mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be s...

Page 14: ...after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the origina...

Page 15: ...0411 HT 3P142639 1 M04B040...

Reviews: