19
Application Information
* The
fi
gures shown in the table are for information purpose only. They should be checked and selected to comply with
the local/national codes of regulations. This is also subject to the type of installation and conductors used.
** The appropriate voltage range should be checked with label data on the unit.
Model
FTXN25/35MV1
FTXN50MV1
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size*
Number of core
mm
2
3.0
3
3.0
3
Interconnection cable size*
Number of core
mm
2
1.5
4
2.5
4
Recommended time delay fuse*
A
25
25
Model
FFQ25CXV1
FFQ35CXV1
FFQ50CXV1
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size*
Number of conductors
mm
2
3.0
3
3.0
3
3.0
3
Interconnection cable size*
Number of conductors
mm
2
1.5
4
1.5
4
2.5
4
Recommended time delay fuse*
A
25
25
25
Model
FDMQ25C2XV1
FDMQ35CXV1
FDMQ50CXV1
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size*
Number of conductors
mm
2
3.0
3
3.0
3
3.0
3
Interconnection cable size*
Number of conductors
mm
2
1.5
4
1.5
4
2.5
4
Recommended time delay fuse*
A
25
25
25
Model
FLQ35EXV1
FLQ50EXV1
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size*
Number of conductors
mm
2
3.0
3
3.0
3
Interconnection cable size*
Number of conductors
mm
2
1.5
4
2.5
4
Recommended time delay fuse*
A
25
25
Summary of Contents for FTXN25MV1B
Page 2: ......
Page 4: ...ii...
Page 36: ...32 Wiring Diagram Indoor Unit Model FTXN25 35MV1 Indoor Unit Model FTXN50MV1...
Page 37: ...33 Wiring Diagram Indoor Unit Model FFQ25 35 50CXV1 Indoor Unit Model FDMQ25 35C2XV1...
Page 38: ...34 Wiring Diagram Indoor Unit Model FDMQ50CXV1 Indoor Unit Model FLQ35EXV1...
Page 39: ...35 Wiring Diagram Indoor Unit Model FLQ50EXV1...
Page 50: ......