14
Application Information
Please ensure that the following steps are taken:
• Check the gradient for drainage
fl
ow as recommended in Figure A.
• Provide clearance for easy servicing and optimal air
fl
ow as shown in Figure B.
• The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm
return air.
• Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit must be a large distance away from the door.
10.0mm
Min 300.0mm
Min 500.0mm
Min 90.0mm
Max 250.0mm
Utensils, Furnitures Or Built-In
Architectural Features Must Not
Protrude More Then 250.0mm
Min 400.0mm
Min 90.0mm
Min 90.0mm
Min 1.0m.
Fig.A
Fig.B
Under ceiling type
Floor standing type