Wiring

Refer to the installation manual for the outdoor unit also.

WARNING

• Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electric shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

CAUTION

Recommend stranded cable for interunit wiring. Local code always supersedes recommendation.

• For stranded wires, make sure to use the round crimp-style terminal for 

connection to the power supply terminal block. Place the round crimp-
style terminals on the wires up to the covered part and secure in place.

• If solid core wire must be used, be sure to curl the end of the lead. 

Improper work may cause heat and fire.

1) Remove the front grille. (Refer to 

“2. Removing and installing 

the front grille”

 on page 11.) 

2) Remove the conduit mounting plate and then secure the 

conduit to the conduit mounting plate with the lock nut, as 
shown in the illustration.

3) Strip wire ends (3/4 inch (20mm)).

4) Match wire colors with terminal numbers on the indoor and 

outdoor unit’s terminal blocks and firmly secure the wires in the 
corresponding terminals with the screws.

5) Connect the ground wires to the corresponding terminals.
6) Pull the wires lightly to make sure they are securely connected.
7) In case of connecting to an adapter system, run the remote 

controller cable and attach the S21. 
(Refer to 

“4. When connecting to an HA system” 

on page 12.)

8) Attach the conduit mounting plate.
9) Shape the wires so that the service lid fits securely.

10) Attach the front grille. (Refer to 

“2. Removing and installing the front 

grille”

 on page 11.) 

11) Take care to ensure that all wiring between the indoor unit and the outdoor unit 

has a consistent connection. Any splices can cause communication errors.

Stranded wire

Round crimp-style 

terminal

Screw

Screw

Flat washer

Flat washer

Good

Wrong

Round 

crimp-style 

terminal

Round crimp-style 

terminal

A

Screw

Round crimp-style 

terminal

Flat washer

Arrow view

 A

Good

Wrong

Back

Terminal block

Electrical wiring box

Wire retainer

Shape wires so that 

the service lid fits 

securely.

Use the specified wire type.

Strip wire ends 

(3/4 inch 

(20mm)).

3/4 inch 

(20mm)

Conduit 

mounting plate

Lock nut

Conduit

Claw

Seat the claw 

onto this part 

and secure

1

2

3

1 2 3

L

1

L

2

Firmly fix the wires with the terminal screws.

Outdoor

unit

Indoor 

unit

Firmly fix the wires with the terminal screws.

Using AWG14 (09/12 class), AWG12 (18/24 

class), stranded and insulated wire for 

connections between indoor and outdoor 

units is recommended. Local codes always 

supersede recommendations.

01_EN_3P686877-1A.fm  8 ページ  2022年6月1日 水曜日 午後12時32分

Summary of Contents for FTXM09WVJU9

Page 1: ...UAL DAIKIN ROOM AIR CONDITIONER R32 Split Series English Fran ais Espa ol MODELS FTXM09WVJU9 FTXM12WVJU9 FTXM18WVJU9 FTXM24WVJU9 Installation manual Manuel d installation Manual de instalaci n 00_CV_3...

Page 2: ...cause serious injury or death Safely dispose all packing and transportation materials in accordance with federal state local laws or ordinances Packing materials such as nails and other metal or wood...

Page 3: ...perty damage Insulate piping to prevent condensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before t...

Page 4: ...use interference with the picture or sound 10 no laundry equipment is nearby 2 Wireless remote controller Turn on all the fluorescent lamps in the room if any and find a location where the remote cont...

Page 5: ...models This is a 09 12 class illustration Do not connect commercially available drain hose directly to the indoor unit Water leakage may result Wrap with the finishing tape so that no gap is left The...

Page 6: ...liquid pipe end and gas pipe end may differ from the distance between those symbols on the mounting plate the distance listed in this manual Always measure the actual distance between the liquid pipe...

Page 7: ...n tape 3 Pass the drain hose and refrigerant pipes through the wall hole then position the indoor unit on the mounting plate hooks using the markings at the top of the indoor unit as a guide 4 Open th...

Page 8: ...e and drain plug 1 Remove the fixing screw and pull out the drain hose How to switch around the drain plug and drain hose Push the drain plug all the way in using a hexagonal wrench 3 16 inch 4mm Hexa...

Page 9: ...in the corresponding terminals with the screws 5 Connect the ground wires to the corresponding terminals 6 Pull the wires lightly to make sure they are securely connected 7 In case of connecting to an...

Page 10: ...se front end When drain hose requires extension obtain an extension hose with an inner diameter of 5 8 inch 16mm Be sure to thermally insulate the indoor section of the extension hose When connecting...

Page 11: ...ation dimensions as below Use separate thermal insulation pipes for gas and liquid refrigerant pipes Using finishing tape bundle and wrap the indoor unit piping and drain hose together so that the dra...

Page 12: ...hing up pull it toward you Installation method 1 Install the front grille and firmly engage the upper hooks 3 locations 2 Install the 3 screws 1 of the front grille and screw covers 2 pcs 2 1 The 18 2...

Page 13: ...the front grille on page 11 2 Remove electrical wiring box cover 1 screw See Fig 5 6 3 Attach the HA connection code Insert HA connection code to HA connector S21 white Wire HA connection code as sho...

Page 14: ...ircuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit...

Page 15: ...14 MEMO 01_EN_3P686877 1A fm 14...

Page 16: ...2205 HT M21B545A The two dimensional bar code is a manufacturing code 3P686877 1A 00_CV_3P686877 1A fm 2...

Reviews: