Refrigerant Piping Work

WARNING

• Do not apply mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the service life of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.
• Never install a dryer to this R32 unit in order to guarantee its service life.
• The drying material may dissolve and damage the system.
• Improper flaring may result in refrigerant gas leakage.

1.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.

2) Remove burrs with the cut surface facing downward, 

so that the filings do not enter the pipe.

3) Put the flare nut on the pipe.

4) Flare the pipe.

5) Check that the flaring has been done correctly.

2.

Refrigerant piping

CAUTION

• Use the flare nut fixed to the main unit. (This is to prevent the flare nut from cracking as a result of deterioration over time.)

• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R32 or R410A.)

• Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

• Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a torque wrench.

Caution on piping handling 

• Protect the open end of the pipe against dust and moisture.
• All pipe bends should be as gentle as possible. Use a pipe bender for bending. 

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following: 
• Insulation material: Polyethylene foam

Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 0.045kcal/mh°C))
Be sure to use insulation that is designed for use with HVAC Systems. 

• ACR Copper only.
• Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as 

below. 

• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
• Using finishing tape, bundle and wrap the indoor unit piping and drain hose together so that the drain hose is below the other piping.

Piping size

Minimum bend radius

Piping thickness

Thermal insulation size

Thermal insulation thickness

Gas side

O.D. 3/8 inch

(9.5mm)

1-3/16 inch (30mm)

or more

0.031 inch (0.8mm)

(C1220T-O)

I.D. 15/32-19/32 inch

(12-15mm)

13/32 inch

(10mm) Min.

O.D. 1/2 inch

(12.7mm)

1-9/16 inch (40mm)

or more

0.031 inch (0.8mm)

(C1220T-O)

I.D. 9/16-5/8 inch

(14-16mm)

O.D. 5/8 inch

(15.9mm)

1-15/16 inch (50mm)

or more

0.039 inch (1.0mm)

(C1220T-O)

I.D. 5/8-13/16 inch

(16-20mm)

Liquid side

O.D. 1/4 inch

(6.4mm)

1-3/16 inch (30mm)

or more

0.031 inch (0.8mm)

(C1220T-O)

I.D. 5/16-13/32 inch

(8-10mm)

A

A

Flaring

Set exactly at the position shown below.

Die

0-0.020 inch

(0-0.5mm)

Clutch-type

Flare tool for 

R32 or R410A

0.039-0.059 inch

(1.0-1.5mm)

Clutch-type

(Rigid-type)

0.059-0.079 inch

(1.5-2.0mm)

Wing-nut type

(Imperial-type)

Conventional flare tool

The flare’s inner surface must be 

flaw-free.
When flaring, do not over-tighten 

and crack.

The pipe end must be evenly flared 

in a perfect circle.

Make sure that the flare nut is fitted.

Check

Cut exactly at 

right angles.

 Remove burrs.

Do not apply refrigeration 

oil to the outer surface.

Flare nut

Apply refrigeration 

oil only to the inner 

surface of the flare.

Do not apply refrigeration 

oil to the flare nut to avoid 

tightening with excessive 

torque.

Apply oil

Torque wrench

Piping union

Flare nut

Spanner

Tighten

Piping size

O.D. 5/8 inch

(15.9mm)

Gas side

Liquid side

O.D. 1/4 inch

(6.4mm)

Flare nut tightening 

torque

45-5/8–55-5/8lbf • ft

(61.8-75.4N • m)

O.D. 1/2 inch

(12.7mm)

36-1/2–44-1/2lbf • ft

(49.5-60.3N • m)

O.D. 3/8 inch

(9.5mm)

24-1/8–29-1/2lbf • ft

(32.7-39.9N • m)

10-1/2–12-3/4lbf • ft

(14.2-17.2N • m)

Wall

If no flare cap is 

available, cover the 

flare mouth with 

tape to keep dirt 

and water out.

Rain

Be sure to 

place a cap.

Gas pipe

Liquid pipe

Gas pipe 

insulation

Liquid pipe 

insulation

Finishing tape Drain hose

01_EN_3P686877-1A.fm  10 ページ  2022年6月1日 水曜日 午後12時32分

Summary of Contents for FTXM09WVJU9

Page 1: ...UAL DAIKIN ROOM AIR CONDITIONER R32 Split Series English Fran ais Espa ol MODELS FTXM09WVJU9 FTXM12WVJU9 FTXM18WVJU9 FTXM24WVJU9 Installation manual Manuel d installation Manual de instalaci n 00_CV_3...

Page 2: ...cause serious injury or death Safely dispose all packing and transportation materials in accordance with federal state local laws or ordinances Packing materials such as nails and other metal or wood...

Page 3: ...perty damage Insulate piping to prevent condensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before t...

Page 4: ...use interference with the picture or sound 10 no laundry equipment is nearby 2 Wireless remote controller Turn on all the fluorescent lamps in the room if any and find a location where the remote cont...

Page 5: ...models This is a 09 12 class illustration Do not connect commercially available drain hose directly to the indoor unit Water leakage may result Wrap with the finishing tape so that no gap is left The...

Page 6: ...liquid pipe end and gas pipe end may differ from the distance between those symbols on the mounting plate the distance listed in this manual Always measure the actual distance between the liquid pipe...

Page 7: ...n tape 3 Pass the drain hose and refrigerant pipes through the wall hole then position the indoor unit on the mounting plate hooks using the markings at the top of the indoor unit as a guide 4 Open th...

Page 8: ...e and drain plug 1 Remove the fixing screw and pull out the drain hose How to switch around the drain plug and drain hose Push the drain plug all the way in using a hexagonal wrench 3 16 inch 4mm Hexa...

Page 9: ...in the corresponding terminals with the screws 5 Connect the ground wires to the corresponding terminals 6 Pull the wires lightly to make sure they are securely connected 7 In case of connecting to an...

Page 10: ...se front end When drain hose requires extension obtain an extension hose with an inner diameter of 5 8 inch 16mm Be sure to thermally insulate the indoor section of the extension hose When connecting...

Page 11: ...ation dimensions as below Use separate thermal insulation pipes for gas and liquid refrigerant pipes Using finishing tape bundle and wrap the indoor unit piping and drain hose together so that the dra...

Page 12: ...hing up pull it toward you Installation method 1 Install the front grille and firmly engage the upper hooks 3 locations 2 Install the 3 screws 1 of the front grille and screw covers 2 pcs 2 1 The 18 2...

Page 13: ...the front grille on page 11 2 Remove electrical wiring box cover 1 screw See Fig 5 6 3 Attach the HA connection code Insert HA connection code to HA connector S21 white Wire HA connection code as sho...

Page 14: ...ircuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit...

Page 15: ...14 MEMO 01_EN_3P686877 1A fm 14...

Page 16: ...2205 HT M21B545A The two dimensional bar code is a manufacturing code 3P686877 1A 00_CV_3P686877 1A fm 2...

Reviews: