background image

6 Installation

Installer reference guide

17

FTXA25~50(A)(B)2V1B(W)(S)(T)(B)
Daikin room air conditioner
4P518023-3F – 2019.10

6.5.4

Specifications of standard wiring
components

Component

Interconnection cable
(indoor↔outdoor)

4-core cable

1.5 mm²~2.5 mm²
and applicable for

220~240 V

H05RN-F (60245 IEC 57)

6.5.5

To connect the electrical wiring on the
indoor unit

Electrical  work  should  be  carried  out  in  accordance  with  the
installation manual and the national electrical wiring rules or code of
practice.

1

Set  the  indoor  unit  on  the  mounting  plate  hooks.  Use  the  " "
marks as a guide.

c

a

b

d

a

Mounting plate (accessory)

b

Piece of packing material

c

Interconnection cable

d

Wire guide

INFORMATION

Support the unit using a piece of packing material.

2

Open  the  front  panel,  and  then  the  service  cover.  Refer  to

"6.2 Opening the indoor unit" 

[

4

 10].

3

Pass  the  interconnection  cable  from  the  outdoor  unit  through
the  feed-through  wall  hole,  through  the  back  of  the  indoor  unit
and through the front side.

Note: 

  In  case  the  interconnection  cable  was  stripped  in  advance,

cover the ends with insulating tape.

4

Bend the end of the cable up.

NOTICE

▪ Be  sure  to  keep  the  power  line  and  transmission  line

apart  from  each  other.  Transmission  wiring  and  power
supply wiring may cross, but may NOT run parallel.

▪ In order to avoid any electrical interference the distance

between  both  wirings  should  ALWAYS  be  at  least
50 mm.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

a
b

c

a

Terminal block

b

Electrical component block

c

Wire retainer

5

Strip the wire ends approximately 15 mm.

6

Match  wire  colours  with  terminal  numbers  on  the  indoor  unit
terminal blocks and firmly screw the wires to the corresponding
terminals.

7

Connect the earth wire to the corresponding terminal.

8

Firmly fix the wires with the terminal screws.

9

Pull  the  wires  to  make  sure  that  they  are  securely  attached,
then retain the wires with the wire retainer.

10

Shape  the  wires  so  that  the  service  cover  fits  securely,  then
close the service cover.

6.5.6

To connect optional accessories (wired
user interface, central user interface, etc.)

1

Remove  the  electrical  wiring  box  cover  (refer  to 

"6.2.7  To

remove the electrical wiring box cover" 

[

4

 12]).

2

Attach  the  connection  cable  to  the  S21  connector  and  pull  the
wire harness as shown in the following figure.

a

a

S21 connector

3

Put  the  electrical  wiring  box  cover  back  and  pull  the  wire
harness around it as shown in the figure above.

6.6

Finishing the indoor unit
installation

6.6.1

To insulate the drain piping, refrigerant
piping and interconnection cable

1

After the drain piping, refrigerant piping and the electrical wiring
are  finished.  Wrap  refrigerant  pipes,  interconnection  cable  and
drain  hose  together  using  insulation  tape.  Overlap  at  least  half
the width of the tape with each turn.

d

e

c

b

f

a

a

Drain hose

b

Interconnection cable

c

Mounting plate (accessory)

d

Refrigerant pipes

e

Indoor unit fixing screw M4×12L (accessory)

f

Bottom frame

Summary of Contents for FTXA50A2V1BW

Page 1: ...1BW FTXA25A2V1BW FTXA35A2V1BW FTXA42A2V1BW FTXA50A2V1BW CTXA15 A B 2V1BS FTXA20 A B 2V1BS FTXA25 A B 2V1BS FTXA35 A B 2V1BS FTXA42 A B 2V1BS FTXA50 A B 2V1BS CTXA15 A B 2V1BT FTXA20 A B 2V1BT FTXA25 A...

Page 2: ...ing 15 6 4 4 Pipe bending guidelines 15 6 4 5 To flare the pipe end 15 6 4 6 To connect the refrigerant piping to the indoor unit 16 6 5 Connecting the electrical wiring 16 6 5 1 About connecting the...

Page 3: ...rks executed on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the pro...

Page 4: ...e for 1 8 m Floor standing units 1 8 x 2 2 m Wall mounted units 2 2 m Ceiling mounted units 3 Use the graph or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 14...

Page 5: ...applicable legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case recharge is required see the nam...

Page 6: ...d When disconnecting the power supply the current carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the term...

Page 7: ...in to the user Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 About the box 3 1 Overview About the box This chapter describes what you...

Page 8: ...nt E g persons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause...

Page 9: ...ause no trouble WARNING Do NOT place objects below the indoor and or outdoor unit that may get wet Otherwise condensation on the unit or refrigerant pipes air filter dirt or drain blockage may cause d...

Page 10: ...multicore cable for power supply cables 6 Installation 6 1 Overview Installation This chapter describes what you have to do and know on site to install the system Typical workflow Installation typical...

Page 11: ...front grille CAUTION Wear protective gloves 1 Open the front panel Refer to 6 2 1 To open the front panel 410 2 Remove the service cover Refer to 6 2 4 To open the service cover 411 3 Remove the wire...

Page 12: ...ew NOTICE When closing the electrical wiring box cover make sure that the tightening torque does NOT exceed 2 0 0 2 N m 6 3 Installing the indoor unit 6 3 1 Precautions when installing the indoor unit...

Page 13: ...half round needle file NOTICE Do NOT use nippers to remove the pipe port cover as this would damage the front grille 6 3 5 To provide drainage Make sure condensation water can be evacuated properly T...

Page 14: ...right side NOTICE Do NOT apply lubricating oil refrigerant oil to the drain plug when inserting it The drain plug may deteriorate and cause drain leakage from the plug a a 4 mm hexagonal wrench 3 Inse...

Page 15: ...nit Regardless of the period INFORMATION Do NOT open the refrigerant stop valve before checking the refrigerant piping When you need to charge additional refrigerant it is recommended to open the refr...

Page 16: ...ing to the indoor unit 4 Connecting the main power supply 6 5 2 Precautions when connecting the electrical wiring INFORMATION Also read the precautions and requirements in the following chapters Gener...

Page 17: ...t that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block...

Page 18: ...ng plate hooks 4 Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4 12L accessory 6 6 4 To install the screw covers 1 Open the front panel and turn the flap up 2 Install...

Page 19: ...cified range Prerequisite Test run may be performed in cooling or heating mode Prerequisite Test run should be performed in accordance with the operation manual of the indoor unit to make sure that al...

Page 20: ...motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core Symbol Meaning PAM Pulse amplitude modulation PCB Printed circuit board PM...

Page 21: ...anual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant...

Page 22: ......

Page 23: ......

Page 24: ...4P518023 3F 2019 10 Copyright 2017 Daikin...

Reviews: