background image

6 Installation

Installer reference guide

13

FTXA25~50(A)(B)2V1B(W)(S)(T)(B)
Daikin room air conditioner
4P518023-3F – 2019.10

e

Use tape measure as shown

f

Tabs for placing a spirit level

g

Unit center

h

Hole for embedded piping Ø65 mm

i

Value for tape measure

j

Position the end of tape measure at symbol " "

k

Drain hose

l

Liquid pipe

m

Gas pipe

6.3.3

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  large  feed-through  hole  in  the  wall  with  a
downward slope towards the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

6.3.4

To remove the pipe port cover

To  connect  the  piping  on  right-side,  right-bottom,  left-side  or  left-
bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

2

Remove  any  burrs  along  the  cut  section  using  a  half  round
needle file.

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

6.3.5

To provide drainage

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe  size.

  If  drain  hose  extension  or  embedded  drain  piping  is

required, use appropriate parts that match the hose front end.

Ø16

Ø18

NOTICE

▪ Install the drain hose with a downward slope.

▪ Traps are NOT permitted.

▪ Do NOT put the end of the hose in water.

Drain  hose  extension.

  To  extend  the  drain  hose,  use  a  field

supplied  hose  with  inner  Ø16  mm.  Do  NOT  forget  to  use  a  heat
insulation tube on the indoor section of the extension hose.

a

a

b

c

Ø16

Ø16

a

Drain hose supplied with the indoor unit

b

Heat insulation tube (field supply)

c

Extension drain hose

Rigid polyvinyl chloride pipe.

 When connecting a rigid polyvinyl

chloride pipe (nominal Ø13 mm) directly to the drain hose as with
embedded piping work, use a field supplied drain socket (nominal
Ø13 mm).

a

b

c

Ø18

a

Drain hose supplied with the indoor unit

b

Drain socket with nominal Ø13 mm (field supply)

c

Rigid polyvinyl chloride pipe (field supply)

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

1

Insert the drain hose in the drain pipe as shown in the following
figure, so it will NOT be pulled out of the drain pipe.

Summary of Contents for FTXA50A2V1BW

Page 1: ...1BW FTXA25A2V1BW FTXA35A2V1BW FTXA42A2V1BW FTXA50A2V1BW CTXA15 A B 2V1BS FTXA20 A B 2V1BS FTXA25 A B 2V1BS FTXA35 A B 2V1BS FTXA42 A B 2V1BS FTXA50 A B 2V1BS CTXA15 A B 2V1BT FTXA20 A B 2V1BT FTXA25 A...

Page 2: ...ing 15 6 4 4 Pipe bending guidelines 15 6 4 5 To flare the pipe end 15 6 4 6 To connect the refrigerant piping to the indoor unit 16 6 5 Connecting the electrical wiring 16 6 5 1 About connecting the...

Page 3: ...rks executed on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the pro...

Page 4: ...e for 1 8 m Floor standing units 1 8 x 2 2 m Wall mounted units 2 2 m Ceiling mounted units 3 Use the graph or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 14...

Page 5: ...applicable legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case recharge is required see the nam...

Page 6: ...d When disconnecting the power supply the current carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the term...

Page 7: ...in to the user Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 About the box 3 1 Overview About the box This chapter describes what you...

Page 8: ...nt E g persons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause...

Page 9: ...ause no trouble WARNING Do NOT place objects below the indoor and or outdoor unit that may get wet Otherwise condensation on the unit or refrigerant pipes air filter dirt or drain blockage may cause d...

Page 10: ...multicore cable for power supply cables 6 Installation 6 1 Overview Installation This chapter describes what you have to do and know on site to install the system Typical workflow Installation typical...

Page 11: ...front grille CAUTION Wear protective gloves 1 Open the front panel Refer to 6 2 1 To open the front panel 410 2 Remove the service cover Refer to 6 2 4 To open the service cover 411 3 Remove the wire...

Page 12: ...ew NOTICE When closing the electrical wiring box cover make sure that the tightening torque does NOT exceed 2 0 0 2 N m 6 3 Installing the indoor unit 6 3 1 Precautions when installing the indoor unit...

Page 13: ...half round needle file NOTICE Do NOT use nippers to remove the pipe port cover as this would damage the front grille 6 3 5 To provide drainage Make sure condensation water can be evacuated properly T...

Page 14: ...right side NOTICE Do NOT apply lubricating oil refrigerant oil to the drain plug when inserting it The drain plug may deteriorate and cause drain leakage from the plug a a 4 mm hexagonal wrench 3 Inse...

Page 15: ...nit Regardless of the period INFORMATION Do NOT open the refrigerant stop valve before checking the refrigerant piping When you need to charge additional refrigerant it is recommended to open the refr...

Page 16: ...ing to the indoor unit 4 Connecting the main power supply 6 5 2 Precautions when connecting the electrical wiring INFORMATION Also read the precautions and requirements in the following chapters Gener...

Page 17: ...t that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block...

Page 18: ...ng plate hooks 4 Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4 12L accessory 6 6 4 To install the screw covers 1 Open the front panel and turn the flap up 2 Install...

Page 19: ...cified range Prerequisite Test run may be performed in cooling or heating mode Prerequisite Test run should be performed in accordance with the operation manual of the indoor unit to make sure that al...

Page 20: ...motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core Symbol Meaning PAM Pulse amplitude modulation PCB Printed circuit board PM...

Page 21: ...anual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant...

Page 22: ......

Page 23: ......

Page 24: ...4P518023 3F 2019 10 Copyright 2017 Daikin...

Reviews: